Parameter list, Simple mode parameter extended mode parameter, Remarks – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual
Page 20: Pr. 77

21
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel (FR-DU07). For details of parameters, refer to the instruction manual.
Simple mode parameter
Extended mode parameter
POINT
Only simple mode parameters are displayed by the initial setting of Pr.160 User group read selection. Set Pr.160
User group read selection as required.
Parameter
Number
Name
Range
Increments
Initial Value
Refer to
page
0
Torque boost
0 to 30%
0.1%
6/4/3/2/1.5/1%
1
Maximum frequency
0 to 120Hz
0.01Hz
120/60Hz
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
7
Acceleration time
0 to 3600/ 360s
0.1/0.01s
5s/15s
8
Deceleration time
0 to 3600/ 360s
0.1/0.01s
10s/30s
9
Electronic thermal O/L relay
0 to 500/ 0 to 3600A
0.01/0.1A
Rated inverter
output current
60
Energy saving control selection
0, 4, 9
1
0
79
Operation mode selection
0, 1, 2, 3, 4, 6, 7
1
0
125
Terminal 2 frequency setting gain frequency 0 to 400Hz
0.01Hz
60Hz
126
Terminal 4 frequency setting gain frequency 0 to 400Hz
0.01Hz
60Hz
160
User group read selection
0, 1, 9999
1
9999
Remarks
⋅ The parameters marked with indicate simple mode parameters.
⋅ The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in
Pr. 77
Parameter write selection.
Function
Parameters
Name
Setting Range
Increments
Initial Value
Refer to
page
B
asi
c f
u
nc
tio
n
s
0
Torque boost
0 to 30%
0.1%
6/4/3/2/1.5/1%
1
Maximum frequency
0 to 120Hz
0.01Hz
120/60Hz
2
Minimum frequency
0 to 120Hz
0.01Hz
0Hz
3
Base frequency
0 to 400Hz
0.01Hz
60Hz
4
Multi-speed setting (high speed)
0 to 400Hz
0.01Hz
60Hz
5
Multi-speed setting (middle speed)
0 to 400Hz
0.01Hz
30Hz
6
Multi-speed setting (low speed)
0 to 400Hz
0.01Hz
10Hz
7
Acceleration time
0 to 3600/ 360s
0.1/0.01s
5s/15s
8
Deceleration time
0 to 3600/ 360s
0.1/0.01s
10s/30s
9
Electronic thermal O/L relay
0 to 500/ 0 to 3600A
0.01/0.1A
Rated inverter
output current
DC In
je
ct
io
n
Br
ak
e
10
DC injection brake operation frequency
0 to 120Hz, 9999
0.01Hz
3Hz
11
DC injection brake operation time
0 to 10s
0.1s
0.5s
12
DC injection brake operation voltage
0 to 30%
0.1%
4/2/1%
13
Starting frequency
0 to 60Hz
0.01Hz
0.5Hz
14
Load pattern selection
0, 1
1
1
Jo
g
o
per
at
io
n
15
Jog frequency
0 to 400Hz
0.01Hz
5Hz
16
Jog acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
0.5s
*1
Differ according to capacities. (55K or less/75K or more)
*2
Differ according to capacities. (0.75K/1.5K to 3.7K/5.5K, 7.5K/11K to 37K/45K, 55K/75K or more)
*3
Differ according to capacities. (7.5K or less/11K or more)
*4
Differ according to capacities. (7.5K or less/11K to 55K/75K or more)
Parameter List