indicates simple mode parameters and

indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Pr.

Pr.

You can use the setting dial of the operation panel (FR-DU07)
like a potentiometer to perform operation.
The key operation of the operation panel can be disabled.

Use these parameters to select/change the input terminal functions.

*1 When Pr. 59 Remote function selection = "1" or "2", the functions of the RL,

RM and RH signals are changed as given in the table.

*2 The OH signal turns on when the relay contact "opens".

You can change the functions of the open collector output
terminal and relay output terminal.

* Setting can be made for the 75K or more.

Operation selection of the
operation panel

Pr.161 Frequency setting/key lock operation selection

Pr.161 Setting

Description

0 (initial value)

Setting dial frequency setting mode

Key lock mode
invalid

1

Setting dial potentiometer mode

10

Setting dial frequency setting mode

Key lock mode
valid

11

Setting dial potentiometer mode

162 to 165

Refer to the section about Pr. 57 and

other relevant parameters.

166, 167

Refer to the section about Pr. 150 and

other relevant parameters.

168, 169

Parameter for manufacturer setting. Do not set.

170, 171

Refer to the section about Pr. 52 and

other relevant parameters.

172 to 174

Refer to the section about Pr. 160 and

other relevant parameters.

Function assignment of
input terminal

Pr.178 STF terminal function selection Pr.179 STR terminal function selection
Pr.180 RL terminal function selection

Pr.181 RM terminal function selection

Pr.182 RH terminal function selection

Pr.183 RT terminal function selection

Pr.184 AU terminal function selection

Pr.185 JOG terminal function selection

Pr.186 CS terminal function selection

Pr.187 MRS terminal function selection

Pr.188 STOP terminal function selection Pr.189 RES terminal function selection

Pr.178 to

Pr.189

Setting

Signal

Name

Function

0

RL

Pr.59 =0
(initial value)

Low speed operation command

Pr.59 =1, 2

*1

Remote setting (setting clear)

1

RM

Pr.59 =0
(initial value)

Middle speed operation
command

Pr.59 =1, 2

*1

Remote setting (deceleration)

2

RH

Pr.59 =0
(initial value)

High speed operation command

Pr.59 =1, 2

*1

Remote setting (acceleration)

3

RT

Second function selection

4

AU

Terminal 4 input selection

5

JOG

Jog operation selection

6

CS

Selection of automatic restart after instantaneous
power failure, flying start

7

OH

External thermal relay input

*2

8

REX

15 speed selection
(combination with three speeds RL, RM, RH)

10

X10

Inverter operation enable signal
(FR-HC, FR-CV connection)

11

X11

FR-HC connection, instantaneous power failure
detection

12

X12

PU operation external interlock

14

X14

PID control valid terminal

16

X16

PU-external operation switchover

24

MRS

Output stop

25

STOP

Start self-holding selection

60

STF

Forward rotation command
(assigned to STF terminal (Pr. 178) only)

61

STR

Reverse rotation command
(assigned to STR terminal (Pr. 179) only)

62

RES

Inverter reset

63

PTC

PTC thermistor input
(assigned to AU terminal (Pr. 184) only)

64

X64

PID forward/reverse action switchover

65

X65

NET/PU operation switchover

66

X66

External/NET operation switchover

67

X67

Command source switchover

9999

No function

Pr.

161

Pr.

Pr.

Pr.

Pr.

Pr.

Pr.

178 to 189

Terminal assignment of
output terminal

Pr.190 RUN terminal function selection Pr.191 SU terminal function selection
Pr.192 IPF terminal function selection

Pr.193 OL terminal function selection

Pr.194 FU terminal function selection

Pr.195 ABC1 terminal function selection

Pr.196 ABC2 terminal function selection

Pr.190 to Pr.196

Setting

Signal

Name

Function

Positive

logic

Negative

logic

0

100

RUN

Inverter running

1

101

SU

Up to frequency

2

102

IPF

Instantaneous power failure/
undervoltage

3

103

OL

Overload alarm

4

104

FU

Output frequency detection

5

105

FU2

Second output frequency
detection

5

105

FU2

Second output frequency
detection

7

107

RBP

Regenerative brake prealarm *

10

110

PU

PU operation mode

11

111

RY

Inverter operation ready

12

112

Y12

Output current detection

13

113

Y13

Zero current detection

14

114

FDN

PID lower limit

15

115

FUP

PID upper limit

16

116

RL

PID forward/reverse rotation
output

17

MC1

Commercial power-supply
switchover MC1

18

MC2

Commercial power-supply
switchover MC2

19

MC3

Commercial power-supply
switchover MC3

25

125

FAN

Fan fault output

26

126

FIN

Heatsink overheat pre-alarm

45

145

RUN3

During inverter running and start
command is on

46

146

Y46

During deceleration at
occurrence of power failure
(retained until release)

47

147

PID

During PID control activated

64

164

Y64

During retry

70

170

SLEEP

During PID output suspension

90

190

Y90

Life alarm

91

191

Y91

Alarm output 3 (power-off signal)

92

192

Y92

Energy saving average value
updated timing

93

193

Y93

Current average monitor signal

94

194

ALM2

Alarm output 2

95

195

Y95

Maintenance timer signal

96

196

REM

Remote output

98

198

LF

Minor fault output

99

199

ALM

Alarm output

9999

No function

232 to 239

Refer to the section about Pr.4 to Pr.6

240

Refer to the section about Pr. 72 and other
relevant parameters.

241

Refer to the section about Pr. 125, Pr.126

242, 243

Refer to the section about Pr. 73 and
other relevant parameters.