Operation selection of the operation panel, Function assignment of input terminal, Terminal assignment of output terminal – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual
Page 40
41
indicates simple mode parameters and
indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr.
Pr.
You can use the setting dial of the operation panel (FR-DU07)
like a potentiometer to perform operation.
The key operation of the operation panel can be disabled.
Use these parameters to select/change the input terminal functions.
*1 When Pr. 59 Remote function selection = "1" or "2", the functions of the RL,
RM and RH signals are changed as given in the table.
*2 The OH signal turns on when the relay contact "opens".
You can change the functions of the open collector output
terminal and relay output terminal.
* Setting can be made for the 75K or more.
Operation selection of the
operation panel
Pr.161 Frequency setting/key lock operation selection
Pr.161 Setting
Description
0 (initial value)
Setting dial frequency setting mode
Key lock mode
invalid
1
Setting dial potentiometer mode
10
Setting dial frequency setting mode
Key lock mode
valid
11
Setting dial potentiometer mode
162 to 165
Refer to the section about Pr. 57 and
other relevant parameters.
166, 167
Refer to the section about Pr. 150 and
other relevant parameters.
168, 169
Parameter for manufacturer setting. Do not set.
170, 171
Refer to the section about Pr. 52 and
other relevant parameters.
172 to 174
Refer to the section about Pr. 160 and
other relevant parameters.
Function assignment of
input terminal
Pr.178 STF terminal function selection Pr.179 STR terminal function selection
Pr.180 RL terminal function selection
Pr.181 RM terminal function selection
Pr.182 RH terminal function selection
Pr.183 RT terminal function selection
Pr.184 AU terminal function selection
Pr.185 JOG terminal function selection
Pr.186 CS terminal function selection
Pr.187 MRS terminal function selection
Pr.188 STOP terminal function selection Pr.189 RES terminal function selection
Pr.178 to
Pr.189
Setting
Signal
Name
Function
0
RL
Pr.59 =0
(initial value)
Low speed operation command
Remote setting (setting clear)
1
RM
Pr.59 =0
(initial value)
Middle speed operation
command
Remote setting (deceleration)
2
RH
Pr.59 =0
(initial value)
High speed operation command
Remote setting (acceleration)
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
6
CS
Selection of automatic restart after instantaneous
power failure, flying start
7
OH
External thermal relay input
8
REX
15 speed selection
(combination with three speeds RL, RM, RH)
10
X10
Inverter operation enable signal
(FR-HC, FR-CV connection)
11
X11
FR-HC connection, instantaneous power failure
detection
12
X12
PU operation external interlock
14
X14
PID control valid terminal
16
X16
PU-external operation switchover
24
MRS
Output stop
25
STOP
Start self-holding selection
60
STF
Forward rotation command
(assigned to STF terminal (Pr. 178) only)
61
STR
Reverse rotation command
(assigned to STR terminal (Pr. 179) only)
62
RES
Inverter reset
63
PTC
PTC thermistor input
(assigned to AU terminal (Pr. 184) only)
64
X64
PID forward/reverse action switchover
65
X65
NET/PU operation switchover
66
X66
External/NET operation switchover
67
X67
Command source switchover
9999
No function
Pr.
161
Pr.
Pr.
Pr.
Pr.
Pr.
Pr.
178 to 189
Terminal assignment of
output terminal
Pr.190 RUN terminal function selection Pr.191 SU terminal function selection
Pr.192 IPF terminal function selection
Pr.193 OL terminal function selection
Pr.194 FU terminal function selection
Pr.195 ABC1 terminal function selection
Pr.196 ABC2 terminal function selection
Pr.190 to Pr.196
Setting
Signal
Name
Function
Positive
logic
Negative
logic
0
100
RUN
Inverter running
1
101
SU
Up to frequency
2
102
IPF
Instantaneous power failure/
undervoltage
3
103
OL
Overload alarm
4
104
FU
Output frequency detection
5
105
FU2
Second output frequency
detection
5
105
FU2
Second output frequency
detection
7
107
RBP
Regenerative brake prealarm *
10
110
PU
PU operation mode
11
111
RY
Inverter operation ready
12
112
Y12
Output current detection
13
113
Y13
Zero current detection
14
114
FDN
PID lower limit
15
115
FUP
PID upper limit
16
116
RL
PID forward/reverse rotation
output
17
MC1
Commercial power-supply
switchover MC1
18
MC2
Commercial power-supply
switchover MC2
19
MC3
Commercial power-supply
switchover MC3
25
125
FAN
Fan fault output
26
126
FIN
Heatsink overheat pre-alarm
45
145
RUN3
During inverter running and start
command is on
46
146
Y46
During deceleration at
occurrence of power failure
(retained until release)
47
147
PID
During PID control activated
64
164
Y64
During retry
70
170
SLEEP
During PID output suspension
90
190
Y90
Life alarm
91
191
Y91
Alarm output 3 (power-off signal)
92
192
Y92
Energy saving average value
updated timing
93
193
Y93
Current average monitor signal
94
194
ALM2
Alarm output 2
95
195
Y95
Maintenance timer signal
96
196
REM
Remote output
98
198
LF
Minor fault output
99
199
ALM
Alarm output
9999
No function
232 to 239
Refer to the section about Pr.4 to Pr.6
240
Refer to the section about Pr. 72 and other
relevant parameters.
241
Refer to the section about Pr. 125, Pr.126
242, 243
Refer to the section about Pr. 73 and
other relevant parameters.
Pr.
190 to 196
Pr.
Pr.
Pr.
Pr.