Ge 57, Peripheral devices list – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual
Page 56
57
Peripheral devices list
Voltage
Motor
Output
(kW)
Applicable Inverter Type
Moulded Case Circuit Breaker (MCCB) *2 or
Earth Leakage Circuit Breaker (ELB)
Input Side Magnetic
Contactor
Recommended Cable
Size (mm
2
Reactor connection
Commercial-power
supply operation
available
Reactor connection
R, S, T
U, V, W
without
with
without
with
200V class
0.75
FR-F720-0.75K
30AF 10A
30AF 10A
30AF 10A
S-N10
S-N10
2
2
1.5
FR-F720-1.5K
30AF 15A
30AF 15A
30AF 15A
S-N10
S-N10
2
2
2.2
FR-F720-2.2K
30AF 20A
30AF 15A
30AF 20A
S-N10
S-N10
2
2
3.7
FR-F720-3.7K
30AF 30A
30AF 30A
30AF 30A
S-N20, N21
S-N10
3.5
3.5
5.5
FR-F720-5.5K
50AF 50A
50AF 40A
50AF 50A
S-N25
S-N20, N21
5.5
5.5
7.5
FR-F720-7.5K
100AF 60A
50AF 50A
100AF 60A
S-N25
S-N25
14
8
11
FR-F720-11K
100AF 75A
100AF 75A
100AF 75A
S-N35
S-N35
14
14
15
FR-F720-15K
225AF 125A
100AF 100A
225AF 125A
S-N50
S-N50
22
22
18.5
FR-F720-18.5K
225AF 150A
225AF 125A
225AF 150A
S-N65
S-N50
38
38
22
FR-F720-22K
225AF 175A
225AF 150A
225AF 175A
S-N80
S-N65
38
38
30
FR-F720-30K
225AF 225A
225AF 175A
225AF 225A
S-N95
S-N80
60
60
37
FR-F720-37K
400AF 250A
225AF 225A
400AF 250A
S-N150
S-N125
80
80
45
FR-F720-45K
400AF 300A
400AF 300A
400AF 350A
S-N180
S-N150
100
100
55
FR-F720-55K
400AF 400A
400AF 350A
600AF 500A
S-N220
S-N180
100
100
75
FR-F720-75K
—
400AF 400A
400AF 400A
—
S-N300
125
125
90
FR-F720-90K
—
400AF 400A
600AF 500A
—
S-N300
150
150
110
FR-F720-110K
—
600AF 500A
600AF 600A
—
S-N400
2
Ч 100
2
Ч 100
400V class
0.75
FR-F740-0.75K
30AF 5A
30AF 5A
30AF 5A
S-N10
S-N10
2
2
1.5
FR-F740-1.5K
30AF 10A
30AF 10A
30AF 10A
S-N10
S-N10
2
2
2.2
FR-F740-2.2K
30AF 10A
30AF 10A
30AF 15A
S-N10
S-N10
2
2
3.7
FR-F740-3.7K
30AF 20A
30AF 15A
30AF 20A
S-N10
S-N10
2
2
5.5
FR-F740-5.5K
30AF 30A
30AF 20A
30AF 30A
S-N20
S-N11, N12
2
2
7.5
FR-F740-7.5K
30AF 30A
30AF 30A
30AF 30A
S-N20
S-N20
3.5
3.5
11
FR-F740-11K
50AF 50A
50AF 40A
50AF 50A
S-N20
S-N20
5.5
5.5
15
FR-F740-15K
100AF 60A
50AF 50A
100AF 60A
S-N25
S-N20
8
8
18.5
FR-F740-18.5K
100AF 75A
100AF 60A
100AF 75A
S-N25
S-N25
14
8
22
FR-F740-22K
100AF 100A
100AF 75A
100AF 100A
S-N35
S-N25
14
14
30
FR-F740-30K
225AF 125A
225AF 100A
225AF 125A
S-N50
S-N50
22
22
37
FR-F740-37K
225AF 150A
225AF 125A
225AF 150A
S-N65
S-N50
22
22
45
FR-F740-45K
225AF 175A
225AF 150A
225AF 175A
S-N80
S-N65
38
38
55
FR-F740-55K
225AF 200A
225AF 175A
225AF 200A
S-N80
S-N80
60
60
75
FR-F740-75K
—
225AF 225A
225AF 225A
—
S-N95
60
60
90
FR-F740-90K
—
225AF 225A
400AF 300A
—
S-N150
60
60
110
FR-F740-110K
—
225AF 225A
400AF 350A
—
S-N180
80
80
132
FR-F740-132K
—
400AF 400A
400AF 400A
—
S-N220
100
125
160
FR-F740-160K
—
400AF 400A
600AF 500A
—
S-N300
125
125
185
FR-F740-185K
—
400AF 400A
600AF 500A
—
S-N300
150
150
220
FR-F740-220K
—
600AF 500A
600AF 600A
—
S-N400
2
Ч 100
2
Ч 100
250
FR-F740-250K
—
600AF 600A
600AF 600A
—
S-N600
2
Ч 100
2
Ч 100
280
FR-F740-280K
—
600AF 600A
800AF 800A
—
S-N600
2
Ч 125
2
Ч 125
315
FR-F740-315K
—
800AF 700A
800AF 800A
—
S-N600
2
Ч 150
2
Ч 150
355
FR-F740-355K
—
800AF 800A
800AF 800A
—
S-N600
2
Ч 200
2
Ч 200
400
FR-F740-400K
—
1000AF 900A
1000AF 1000A
—
S-N800
2
Ч 200
2
Ч 200
450
FR-F740-450K
—
1000AF 1000A
1000AF 1000A
—
1000A rated
product
2
Ч 250
2
Ч 250
500
FR-F740-500K
—
1200AF 1200A
1200AF 1200A
—
1000A rated
product
2
Ч 250
2
Ч 250
560
FR-F740-560K
—
1600AF 1500A
1600AF 1600A
—
1200A rated
product
3
Ч 200
3
Ч 200
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage 200VAC (200V class)/400VAC (400V class) 50Hz.
*2
Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to the Instruction Manual (basics).)
*3
The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is used for emergency stop during motor driving, the electrical durability is 25
times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class AC-3 rated
current for the motor rated current.
*4
Cable
For the 55K or less, the recommended cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature
of 75
°C. Assumes that the ambient temperature is 50°C or less and the wiring distance is 20m or less.
For the 75K or more, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable) etc.) with continuous
maximum permissible temperature of 90
°C or more. Assumes that the ambient temperature is 50°C or less and wiring is performed in an enclosure.
MCCB
INV
MCCB
INV
IM
IM