indicates simple mode parameters and

indicates extended parameters. When setting parameters, refer to the instruction manual (applied) and understand instructions.

Pr.

Pr.

Set the current of the electronic overcurrent protection to protect
the motor from overheat.This feature provides the optimum
protective characteristics, including reduced motor cooling
capability, at low speed.

This function detects the overload (overheat) of the motor, stops
the operation of the inverter's output transistor, and stops the
output.
Set the rated current [A] of the motor in Pr.9.
When using a motor with an external thermal relay, etc., set “0” in
Pr. 9 to make the electronic thermal relay function invalid. (Note
that the output transistor protection of the inverter (E.THT)
functions.)
When using the Mitsubishi constant-torque motor
1) Set “1” in Pr.71 .

(This provides a 100% continuous torque characteristic in the
low-speed range.)

2) Set the rated motor current in Pr. 9.
When the RT signal is on, thermal protection is provided based on
the Pr. 51 setting.
Use this function when rotating two motors of different rated
currents individually by a single inverter.

(When rotating two motors

together, use external thermal relays.)

The DC injection brake can be operated at a motor stop to adjust
the stop timing and braking torque.

You can set the starting frequency and hold the set starting
frequency for a certain period of time.
Set these functions when you need the starting torque or want
smooth motor drive at a start.

You can select the optimum output characteristic (V/F
characteristic) for the application and load characteristics.

You can set the frequency and acceleration/decelertion time for
jog operation. Jog operation can be performed from either the
outside or PU.
Can be used for conveyor positioning, test operation, etc.

The inverter output can be shut off by the MRS signal. The logic
of the MRS signal can also be selected.

Motor protection from overheat
(electronic thermal relay function)

Pr.51 Second electronic thermal O/L relay

DC injection brake

Pr.10 DC injection brake operation frequency

Pr.11 DC injection brake operation time

Pr.12 DC injection brake operation voltage

* If the Pr. 71 initial value is changed

to the setting for use with a

constant-torque motor, the Pr. 12

setting changes to the

corresponding value in the above

table.

Starting frequency

Pr.13 Starting frequency

Pr.571 Holding time at a start

Pr.

9

Pr.

51

Pr.9 Electronic thermal O/L relay

Pr.

10 to 12

Time

Pr

.10

Operation

frequency

Time

Pr.12
Operation
voltage

voltage

Pr.11 Operation time

Output frequency (Hz)

DC injection
brake

Pr.12 Initial

Value

When

Using the
Mitsubish

Constant

Torque

Motor

When
Using

the

Energy

Saving

Motor

3.7K or less 4%

5.5K to 7.5K 4%

2% *

3%

11K or more 2%

75K or more 1%

Pr.

13, 571

Output
frequency
(Hz)

Time

Pr.13

Pr.571 setting time

Forward
rotation

ON

0

60

Setting range

V/F pattern matching applications

Pr. 14 Load pattern selection

Setting “0”

For constant-torque load

Setting “1” (initial value)

For variable-torque load

Jog operation

Pr.15 Jog frequency

Pr.16 Jog acceleration/deceleration time

Logic selection of output stop
signal (MRS)

Pr.17 MRS input selection

18

Refer to the section about Pr.1, Pr.2

19

Refer to the section about Pr. 3.

20, 21

Refer to the section about Pr.7, Pr.8

Pr.

14

100%

Output voltage

Pr.3 Base frequency

Output frequency (Hz)

100%

Output voltage

Pr.3 Base frequency

Output frequency (Hz)

Pr.

15, 16

Output
frequency
(Hz) Pr.20

Pr.15

Jog frequency

setting range

Pr.16

Forward
rotation

Reverse
rotation

Time

ON

ON

ON

JOG signal

Forward
rotation STF

Reverse
rotation STR

Pr.

17

ON

ON

MRS signal

STF (STR)
signal

Motor coasts
to stop

Time

(Initial
value)

Output
stop

Output
stop

MRS

SD (PC)

Inverter

MRS

SD (PC)

Inverter

Setting value "0"

Setting value "2"

Pr.

Pr.

Pr.