Ge 51, Stand-alone option, Name (type) specifications, structure, etc – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual
Page 50
51
Stand-alone option
Name (type)
Specifications, Structure, etc.
Intercompatibility
attachment
FR-AAT
FR-A5AT
FR-F500 series intercompatibility attachment
The FR-F700 series inverter can be installed using installation holes of the conventional FR-F500 series with this attachment.This attachment is use-
ful for replacing the conventional model with the FR-F700 series.
Since the installation size of the 400V class 0.75K to 3.7K, 7.5K, 22K, 37K to 55K are the same, an intercompatibility attachment is not necessary
* The depth increases after installation of the inverter when the attachment is used.
FR-A100E and FR-A200E series installation intercompatibility attachment
The FR-F700 series inverter can be installed using installation holes of the conventional FR-A100E and FR-A200E series with this attachment. This
attachment is useful for replacing the conventional model with the FR-F700 series.
* The depth increases after installation of the inverter when the attachment is used
AC reactor
(for power coordination)
FR-HAL-(H)
K
Outline dimension
DC reactor
(for power coordination)
FR-HEL-(H)
K
Outline dimension
Inverter
FR-AAT
12
Type
Applied Inverter
FR-AAT22
FR-F740-5.5K
FR-AAT24
FR-F740-15K, 18.5K
FR-AAT27
FR-F740-30K
Inverter
FR-A5AT
12
Type
Applied Inverter
FR-A5AT02
FR-F740-0.75K to 3.7K
FR-A5AT03
FR-F740-5.5K to 11K
FR-A5AT04
FR-F740-15K to 22K
FR-A5AT05
FR-F740-45K, 55K
(Unit: mm)
Type
W
D
H
Mass
(kg)
Type
W
D
H
Mass
(kg)
2
0
0
V
0.4K
104
72
99
0.6
4
0
0
V
H0.4K
135
59.6
115
1.5
0.75K
104
74
99
0.8
H0.75K
135
59.6
115
1.5
1.5K
104
77
99
1.1
H1.5K
135
59.6
115
1.5
2.2K
115
77
115
1.5
H2.2K
135
59.6
115
1.5
3.7K
115
83
115
2.2
H3.7K
135
70.6
115
2.5
5.5K
115
83
115
2.3
H5.5K
160
72
142
3.5
7.5K
130
100
135
4.2
H7.5K
160
91
142
5.0
11K
160
111
164
5.2
H11K
160
91
146
6.0
15K
160
126
167
7.0
H15K
220
105
195
9.0
18.5K
160
175
128
7.1
H18.5K
220
170
215
9.0
22K
185
158
150
9.0
H22K
220
170
215
9.5
30K
185
168
150
9.7
H30K
220
170
215
11
37K
210
174
175
12.9
H37K
220
170
214
12.5
45K
210
191
175
16.4
H45K
280
165
245
15
55K
210
201
175
17.4
H55K
280
170
245
18
H75K
205
208
170
20
(Note) 1. Make selection according to the applied
motor capacity. (When the inverter
capacity is larger than the motor
capacity, make selection according to the
motor capacity)
2. Power factor improving reactor (FR-BAL)
can be used.
Power factor improving effect
FR-BAL : approx. 90%
FR-HAL : approx. 88%
H
W
Less than D
(Unit: mm)
Type
W
D
H
Mass
(kg)
Type
W
D
H
Mass
(kg)
2
0
0
V
0.4K
70
61
71
0.4
4
0
0
V
H0.4K
90
60
78
0.6
0.75K
85
61
81
0.5
H0.75K
66
70
100
0.8
1.5K
85
70
81
0.8
H1.5K
66
80
100
1
2.2K
85
70
81
0.9
H2.2K
76
80
110
1.3
3.7K
77
82
92
1.5
H3.7K
86
95
120
2.3
5.5K
77
92
92
1.9
H5.5K
96
100
128
3
7.5K
86
98
113
2.5
H7.5K
96
105
128
3.5
11K
105
112
133
3.3
H11K
105
110
137
4.5
15K
105
115
133
4.1
H15K
105
125
152
5
18.5K
105
165
93
4.7
H18.5K
114
120
162
5
22K
105
175
93
5.6
H22K
133
120
178
6
30K
114
200
100
7.8
H30K
133
120
178
6.5
37K
133
195
117
10
H37K
133
155
187
8.5
45K
133
205
117
11
H45K
133
170
187
10
55K
153
209
132
12.6
H55K
152
170
206
11.5
(Note) 1.Be sure to remove the jumper across
terminals P/+ - P1 of the inverter. (A
failure to do so will produce no power
factor improving effect)
2. The wiring length between the reactor and
inverter should be within 5m.
3. The size of the cables used should be equal
to or larger than that of the power supply
cables (R/L1, S/L2, T/L3).
4. Make selection according to the motor
capacity.
(When the inverter capacity is larger than
the motor capacity, make selection
according to the motor capacity)
5. Power factor improving reactor (FR-BEL)
can be used.
Power factor improving effect
FR-BEL : approx. 95%
FR-HEL : approx. 93%
H
W
Less than D