MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual
Page 22
23
66
Stall prevention operation reduction
starting frequency
0 to 400Hz
0.01Hz
60Hz
Re
try
67
Number of retries at alarm occurrence
0 to 10, 101 to 110
1
0
68
Retry waiting time
0 to 10s
0.1s
1s
69
Retry count display erase
0
1
0
70
Special regenerative brake duty
0 to 10%
0.1%
0%
71
Applied motor
0, 1, 2, 20
1
0
72
PWM frequency selection
0 to 15/0 to 6, 25
1
2
73
Analog input selection
0 to 7, 10 to 17
1
1
74
Input filter time constant
0 to 8
1
1
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17
1
14
76
Alarm code output selection
0, 1, 2
1
0
77
Parameter write selection
0, 1, 2
1
0
78
Reverse rotation prevention selection
0, 1, 2
1
0
79
Operation mode selection
0, 1, 2, 3, 4, 6, 7
1
0
Sim
ple
m
a
gne
tic
fl
ux
ve
ct
or
co
nt
ro
l
80
Motor capacity (simple magnetic flux
vector control)
0.4 to 55kW, 9999
/0 to 3600kW, 9999
0.01/0.1kW
9999
90
Motor constant (R1)
0 to 50
Ω, 9999
/0 to 400m
Ω, 9999
0.001
Ω/
0.01m
9999
Adj
us
tabl
e 5
p
oi
nt
s V/
F
100
V/F1 (first frequency)
0 to 400Hz, 9999
0.01Hz
9999
101
V/F1 (first frequency voltage)
0 to 1000V
0.1V
0V
102
V/F2 (second frequency)
0 to 400Hz, 9999
0.01Hz
9999
103
V/F2 (second frequency voltage)
0 to 1000V
0.1V
0V
104
V/F3 (third frequency)
0 to 400Hz, 9999
0.01Hz
9999
105
V/F3 (third frequency voltage)
0 to 1000V
0.1V
0V
106
V/F4 (fourth frequency)
0 to 400Hz, 9999
0.01Hz
9999
107
V/F4 (fourth frequency voltage)
0 to 1000V
0.1V
0V
108
V/F5 (fifth frequency)
0 to 400Hz, 9999
0.01Hz
9999
109
V/F5 (fifth frequency voltage)
0 to 1000V
0.1V
0V
P
U
c
on
nec
to
r
co
m
m
uni
ca
tio
n
117
PU communication station
0 to 31
1
0
118
PU communication speed
48, 96, 192, 384
1
192
119
PU communication stop bit length.
0, 1, 10, 11
1
1
120
PU communication parity check
0, 1, 2
1
2
121
Number of PU communication retries
0 to 10, 9999
1
1
122
PU communication check time interval
0, 0.1 to 999.8s, 9999
0.1s
9999
123
PU communication waiting time setting
0 to 150ms, 9999
1
9999
124
PU communication CR/LF presence/
absence selection
0, 1, 2
1
1
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
PI
D
ope
ra
tion
127
PID control automatic switchover
freqeuncy
0 to 400Hz, 9999
0.01Hz
9999
128
PID action selection
10, 11, 20, 21, 50, 51, 60,
61
1
10
129
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
130
PID integral time
0.1 to 3600s, 9999
0.1s
1s
131
PID upper limit
0 to 100%, 9999
0.1%
9999
132
PID lower limit
0 to 100%, , 9999
0.1%
9999
133
PID action set point
0 to 100%, 9999
0.01%
9999
134
PID differential time
0.01 to 10.00s, 9999
0.01s
9999
*1
Differ according to capacities. (55K or less/75K or more)
*2
Setting can be made for the 75K or more.
Function
Parameters
Name
Setting Range
Increments
Initial Value
Refer to
page