22
17
MRS input selection
0, 2
1
0
18
High speed maximum frequency
120 to 400Hz
0.01Hz
120/60Hz
19
Base frequency voltage
0 to 1000V, 8888, 9999
0.1V
9999
Acc
eler
ation
and
de
cel
er
at
ion
time
s
20
Acceleration/deceleration reference
frequency
1 to 400Hz
0.01Hz
60Hz
21
Acceleration/deceleration time
increments
0, 1
1
0
St
al
l
pr
eve
nt
ion
22
Stall prevention operation level
0 to 150%, 9999
0.1%
120%
23
Stall prevention operation level
compensation factor at double speed
0 to 200%, 9999
0.1%
9999
Mu
lti-
sp
e
ed
se
tti
ng
24 to 27
Multi-speed setting 4 speed to 7 speed
0 to 400Hz, 9999
0.01Hz
9999
28
Multi-speed input compensation
selection
0, 1
1
0
29
Acceleration/deceleration pattern
selection
0, 1, 2, 3
1
0
30
Regenerative function selection
0, 2/0, 1, 2
1
0
Fr
eq
uen
cy
ju
m
p
31
Frequency jump 1A
0 to 400Hz, 9999
0.01Hz
9999
32
Frequency jump 1B
0 to 400Hz, 9999
0.01Hz
9999
33
Frequency jump 2A
0 to 400Hz, 9999
0.01Hz
9999
34
Frequency jump 2B
0 to 400Hz, 9999
0.01Hz
9999
35
Frequency jump 3A
0 to 400Hz, 9999
0.01Hz
9999
36
Frequency jump 3B
0 to 400Hz, 9999
0.01Hz
9999
37
Speed display
0, 1 to 9998
1
0
F
re
que
nc
y
de
te
ct
io
n
41
Up-to-frequency sensitivity
0 to 100%
0.1%
10%
42
Output frequency detection
0 to 400Hz
0.01Hz
6Hz
43
Output frequency detection for reverse
rotation
0 to 400Hz, 9999
0.01Hz
9999
Sec
ond
fu
nct
ion
s
44
Second acceleration/deceleration time
0 to 3600/360s
0.1/0.01s
5s
45
Second deceleration time
0 to 3600/360s, 9999
0.1/0.01s
9999
46
Second torque boost
0 to 30%, 9999
0.1%
9999
47
Second V/F (base frequency)
0 to 400Hz, 9999
0.01Hz
9999
48
Second stall prevention operation
current
0 to 150%
0.1%
120%
49
Second stall prevention operation
frequency
0 to 400Hz, 9999
0.01Hz
0Hz
50
Second output frequency detection
0 to 400Hz
0.01Hz
30Hz
51
Second electronic thermal O/L relay
0 to 500A, 9999 /
0 to 3600A, 9999
0.01/0.1A
9999
M
on
ito
r f
un
cti
o
ns
52
DU/PU main display data selection
0, 5, 6, 8 to 14, 17, 20, 23
to 25, 50 to 57, 100
1
0
54
FM terminal function selection
1 to 3, 5, 6, 8 to 14, 17, 21,
24, 50, 52, 53
1
1
55
Frequency monitoring reference
0 to 400Hz
0.01Hz
60Hz
56
Current monitoring reference
0 to 500/0 to 3600A
0.01/0.1A
Rated inverter
output current
Autom
a
tic
re
st
a
rt
fu
n
ctio
ns
57
Restart coasting time
0, 0.1 to 5s, 9999/
0, 0.1 to 30s, 9999
0.1s
9999
58
Restart cushion time
0 to 60s
0.1s
1s
59
Remote function selection
0, 1, 2, 3
1
0
60
Energy saving control selection
0, 4, 9
1
0
65
Retry selection
0 to 5
1
0
*1
Differ according to capacities. (55K or less/75K or more)
Function
Parameters
Name
Setting Range
Increments
Initial Value
Refer to
page