beautypg.com

Caution – MITSUBISHI ELECTRIC INVERTER FR-F700 User Manual

Page 17

background image

Features

Standard

Specifications

Outline

Dimension

Drawings

Operation

Panel

Protective

Functions

Options

Instructions

Motor

Compatibility

W

arranty

Inquiry

Peripheral Devices

Why energy

savings?

Te

rminal Connection

Diagram

Te

rminal Specification

Explanation

Parameter

List

Explanations

of

Parameters

18

Con

tr

o

l c

irc

uit

out

put

s

igna

l

Re

lay

A1, B1, C1

Relay output 1 (alarm
output)

Changeover contact output indicates that the inverter protective function has activated and the
output stopped. Abnormal: No conduction across B-C (Across A-C Continuity), Normal: Across
B-C Continuity (No conduction across A-C) Contact capacity: 230VAC 0.3A (Power factor=0.4)
30VDC 0.3A

A2, B2, C2

Relay output 2

1 changeover contact output Contact capacity: 230VAC 0.3A (Power factor=0.4) 30VDC 0.3A

O

pen

c

o

llec

to

r

RUN

Inverter running

Switched low when the inverter output frequency is equal to or
higher than the starting frequency (initial value 0.5Hz). Switched
high during stop or DC injection brake operation.

*1

Permissible load 24VDC
0.1A
(a voltage drop is 3.4V
maximum when the signal
is on)

Alarm code (4bit) output
(Refer to page 36)

SU

Up to frequency

Switched low when the output frequency reaches within the range
of ±10% (initial value) of the set frequency. Switched high during
acceleration/deceleration and at a stop.

*1

OL

Overload alarm

Switched low when stall prevention is activated by the stall
prevention function. Switched high when stall prevention is
cancelled.

*1

IPF

Instantaneous power
failure

Switched low when an instantaneous power failure and under
voltage protections are activated.

*1

FU

Frequency detection

Switched low when the inverter output frequency is equal to or
higher than the preset detected frequency and high when less than
the preset detected frequency.

*1

SE

Open collector output
common

Common terminal for terminals RUN, SU, OL, IPF, FU

Pul

se

FM

For meter

Select one e.g. output frequency from monitor items. *2
The output signal is proportional to the magnitude of the
corresponding monitoring item.

Output item:
Output frequency (initial
setting)
Permissible load current
2mA
1440 pulses/s at 60Hz

A

nalo

g

AM

Analog signal output

Output item:
Output frequency (initial
setting)
Output signal 0 to 10VDC
Permissible load current
1mA (load impedance
10k

Ω or more) Resolution

8 bit

Commun

ic

a

tion

PU connector

PU connector

With the PU connector, communication can be made through RS-485.
(for connection on a 1:1 basis only)
. Conforming standard

: EIA-485(RS-485)

. Transmission format

: Multidrop

. Communication speed : 4800 to 38400bps
. Overall length

: 500m

RS-485
terminal

TXD+

Inverter transmission
terminal

With the RS-485 terminal, communication can be made through RS-485.
Conforming standard

: EIA-485 (RS-485)

Transmission format

: Multidrop link

Communication speed

: 300 to 38400bps

Overall length

: 500m

TXD-

RXD+

Inverter reception
terminal

RXD-

SG

Earth (Ground)

CAUTION

The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.

indicates that terminal functions can be selected fromPr. 178 to Pr. 196 (I/O terminal function selection)

*1. Low indicates that the open collector output transistor is on (conducts). High indicates that the transistor is off (does not conduct).
*2. Not output during inverter reset.

Type

Terminal Symbol

Terminal Name

Description