7 clear data, Clear data -11 – GE 489 User Manual
Page 61

GE Multilin
489 Generator Management Relay
4-11
4 SETPOINTS
4.2 S1 489 SETUP
4
4.2.7 CLEAR DATA
PATH: SETPOINTS
Ö
S1 489 SETUP
ÖØ
CLEAR DATA
These commands may be used to clear various historical data.
•
CLEAR LAST TRIP DATA: The Last Trip Data may be cleared by executing this command.
•
CLEAR MWh and Mvarh METERS: Executing this command will clear the MWh and Mvarh metering to zero.
•
CLEAR PEAK DEMAND DATA: Execute this command to clear peak demand values.
•
CLEAR RTD MAXIMUMS: All maximum RTD temperature measurements are stored and updated each time a new
maximum temperature is established. Execute this command to clear the maximum values.
•
CLEAR ANALOG I/P MIN/MAX: The minimum and maximum analog input values are stored for each Analog Input.
Those minimum and maximum values may be cleared at any time.
•
CLEAR TRIP COUNTERS: There are counters for each possible type of trip. Those counters may be cleared by exe-
cuting this command.
•
CLEAR EVENT RECORD: The event recorder saves the last 40 events, automatically overwriting the oldest event. If
desired, all events can be cleared using this command to prevent confusion with old information.
•
CLEAR GENERATOR INFORMATION: The number of thermal resets and the total generator running hours can be
viewed in actual values. On a new installation, or if new equipment is installed, this information is cleared through this
setpoint.
•
CLEAR BREAKER INFORMATION: The total number of breaker operations can be viewed in actual values. On a new
installation or if maintenance work is done on the breaker, this accumulator can be cleared with this setpoint.
CLEAR DATA
[ENTER] for more
CLEAR LAST TRIP
DATA: No
Range: No, Yes
RESET MWh and Mvarh
METERS: No
Range: No, Yes
CLEAR PEAK DEMAND
DATA: No
Range: No, Yes
CLEAR RTD
MAXIMUMS: No
Range: No, Yes
CLEAR ANALOG I/P
MIN/MAX: No
Range: No, Yes
CLEAR TRIP
COUNTERS: No
Range: No, Yes
CLEAR EVENT
RECORD: No
Range: No, Yes
CLEAR GENERATOR
INFORMATION: No
Range: No, Yes
CLEAR BREAKER
INFORMATION: No
Range: No, Yes
ENTER
ESCAPE
р
р
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE