GE Multilin
489 Generator Management Relay
7-11
7 TESTING
7.3 ADDITIONAL FUNCTIONAL TESTS
7
7.3.3 REACTIVE POWER ACCURACY
The specification for reactive power is
±1% of
Ч 2 Ч CT × VT × VT
full scale
at I
avg
< 2 × CT. Perform the steps below to
verify accuracy and trip element.
1.
Alter the following system setpoints:
S2 SYSTEM SETUP
Ö
CURRENT SENSING
Ö
PHASE CT PRIMARY:
"5000"
S2 SYSTEM SETUP
ÖØ
VOLTAGE SENSING
Ö
VT CONNECTION TYPE:
"Wye"
S2 SYSTEM SETUP
ÖØ
VOLTAGE SENSING
ÖØ
VOLTAGE TRANSFORMER RATIO:
"100:1"
S2 SYSTEM SETUP
ÖØ
GEN. PARAMETERS
Ö
GENERATOR RATED MVA:
"100"
S2 SYSTEM SETUP
ÖØ
GEN. PARAMETERS
ÖØ
GENERATOR RATED POWER FACTOR:
"0.85"
S2 SYSTEM SETUP
ÖØ
GEN. PARAMETERS
ÖØ
GENERATOR VOLTAGE PHASE-PHASE:
"12000"
The rated reactive power is
.
2.
Alter the following reactive power setpoints:
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
REACTIVE POWER ALARM:
"Unlatched"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
ASSIGN ALARM RELAYS(2-5):
"---5"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
POSTIVE Mvar ALARM LEVEL:
"0.6 x Rated"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
NEGATIVE Mvar ALARM LEVEL:
"0.6 x Rated"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
REACTIVE POWER ALARM DELAY:
"5 s"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
REACTIVE POWER ALARM EVENT:
"On"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
REACTIVE POWER TRIP: "
Unlatched"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
ASSIGN TRIP RELAYS(1-4):
"1---"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
POSTIVE Mvar TRIP LEVEL:
"0.75 x Rated"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
NEGATIVE Mvar TRIP LEVEL:
"0.75 x Rated"
S7 POWER ELEMENTS
Ö
REACTIVE POWER
ÖØ
REACTIVE POWER TRIP DELAY:
"10 s"
3.
Inject current and apply voltage as per the table below. Verify the alarm/trip elements and the accuracy of the mea-
sured values. View the measured values in:
A2 METERING DATA
Ö
POWER METERING
4.
View the Event Records in
A5 EVENT RECORD
CURRENT/
VOLTAGE
MVAR
ALARM
TRIP
EXPECTED TOLERANCE MEASURED EXPECTED OBSERVED
DELAY
EXPECTED OBSERVED
DELAY
Vab=120V
∠0°
Vbc=120V
∠120°lag
Vca=120V
∠240°lag
Ian=5 A
∠10°lag
Ibn=5 A
∠130°lag
Icn=5 A
∠250°lag
18
13 to 23
N/A
N/A
Vab=120V
∠0°
Vbc=120V
∠120°lag
Vca=120V
∠240°lag
Ian=5 A
∠340°lag
Ibn=5 A
∠100°lag
Icn=5 A
∠220°lag
–35
–40 to –30
N/A
Vab=120V
∠0°
Vbc=120V
∠120°lag
Vca=120V
∠240°lag
Ian=5 A
∠330°lag
Ibn=5 A
∠90°lag
Icn=5 A
∠210°lag
–52
–57 to –47
Vab=120V
∠0°
Vbc=120V
∠120°lag
Vca=120V
∠240°lag
Ian=5 A
∠30°lag
Ibn=5 A
∠150°lag
Icn=5 A
∠270°lag
52
47 to 57
: Activated, : Not Activated
3
100
cos
1
–
0.85
(
)
(
)
sin
52.7 Mvar
±
=