Hardware functional tests, 1 output current accuracy, 2 phase voltage input accuracy – GE 489 User Manual
Page 215: 2 hardware functional tests, Output current accuracy -3, Phase voltage input accuracy -3

GE Multilin
489 Generator Management Relay
7-3
7 TESTING
7.2 HARDWARE FUNCTIONAL TESTS
7
7.2HARDWARE FUNCTIONAL TESTS
7.2.1 OUTPUT CURRENT ACCURACY
The specification for output and neutral end current input is
±0.5% of 2 × CT when the injected current is less than 2 × CT.
Perform the steps below to verify accuracy.
1.
Alter the following setpoint:
S2 SYSTEM SETUP
Ö
CURRENT SENSING
Ö
PHASE CT PRIMARY:
"1000 A"
2.
Measured values should be
±10 A. Inject the values shown in the table below and verify accuracy of the measured val-
ues. View the measured values in:
A2 METERING DATA
ÖØ
CURRENT METERING
7.2.2 PHASE VOLTAGE INPUT ACCURACY
The specification for phase voltage input accuracy is
±0.5% of full scale (200 V). Perform the steps below to verify accu-
racy.
1.
Alter the following setpoints:
S2 SYSTEM SETUP
ÖØ
VOLTAGE SENSING
Ö
VT CONNECTION TYPE:
"Wye"
S2 SYSTEM SETUP
ÖØ
VOLTAGE SENSING
ÖØ
VOLTAGE TRANSFORMER RATIO:
"10.00:1"
2.
Measured values should be
±1.0 V. Apply the voltage values shown in the table and verify accuracy of the measured
values. View the measured values in:
A2 METERING DATA
ÖØ
VOLTAGE METERING
INJECTED CURRENT
EXPECTED
CURRENT
MEASURED CURRENT
1 A UNIT
5 A UNIT
PHASE A
PHASE B
PHASE C
0.1 A
0.5 A
100 A
0.2 A
1.0 A
200 A
0.5 A
2.5 A
500 A
1 A
5 A
1000 A
1.5 A
7.5 A
1500 A
2 A
10 A
2000 A
APPLIED LINE-
NEUTRAL VOLTAGE
EXPECTED VOLTAGE
READING
MEASURED VOLTAGE
A-N
B-N
C-N
30 V
300 V
50 V
500 V
100 V
1000 V
150 V
1500 V
200 V
2000 V
270 V
2700 V