2 implementation table, Implementation table -41 – GE 489 User Manual
Page 203

GE Multilin
489 Generator Management Relay
6-41
6 COMMUNICATIONS
6.4 DNP PROTOCOL
6
6.4.2 IMPLEMENTATION TABLE
The table below gives a list of all objects recognized and returned by the relay. Additional information is provided on the fol-
lowing pages including a list of the default variations returned for each object and lists of defined point numbers for each
object.
Table 6–3: DNP IMPLEMENTATION TABLE
OBJECT
DESCRIPTION
REQUEST
RESPONSE
OBJ
VAR
FUNC.
CODES
QUAL.
CODES
(HEX)
FUNC.
CODES
QUAL.
CODES
(HEX)
1
0
Binary Input - All Variations
1
06
1
1
Binary Input
1
00, 01, 06
129
00, 01
1
2
Binary Input With Status
1
00, 01, 06
129
00, 01
2
0
Binary Input Change - All Variations
1
06, 07, 08
2
1
Binary Input Change Without Time
1
06, 07, 08
129
17, 28
2
2
Binary Input Change With Time
1
06, 07, 08
129
17, 28
10
0
Binary Output - All Variations
1
06
10
2
Binary Output Status
1
00, 01, 06
129
00, 01
12
1
Control Relay Output Block
5, 6
17, 28
129
17, 28
20
0
Binary Counter - All Variations
1,7,8,9,10
06
129
00, 01
20
5
32-Bit Binary Counter without Flag
1,7,8,9,10
06
129
00, 01
20
6
16-Bit Binary Counter without Flag
1,7,8,9,10
06
129
00, 01
21
0
Frozen Counter - All Variations
1
06
129
00, 01
21
9
32-Bit Frozen Counter without Flag
1
06
129
00, 01
21
10
16-Bit Frozen Counter without Flag
1
06
129
00, 01
30
0
Analog Input - All Variations
1
06
30
1
32-Bit Analog Input With Flag
1
00, 01, 06
129
00, 01
30
2
16-Bit Analog Input With Flag
1
00, 01, 06
129
00, 01
30
3
32-Bit Analog Input Without Flag
1
00, 01, 06
129
00, 01
30
4
16-Bit Analog Input Without Flag
1
00, 01, 06
129
00, 01
32
0
Analog Input Change - All Variations
1
06, 07, 08
32
1
32-Bit Analog Input Change Without Time
1
06, 07, 08
129
17, 28
32
2
16-Bit Analog Input Change Without Time
1
06, 07, 08
129
17, 28
32
3
32-Bit Analog Input Change With Time
1
06, 07, 08
129
17, 28
32
4
16-Bit Analog Input Change With Time
1
06, 07, 08
129
17, 28
50
1
Time and Date
1, 2
07 (Note 1)
129
07
60
1
Class 0 Data (Note 2)
1
06
129
60
2
Class 1 Data (Note 3)
1
06, 07, 08
129
60
3
Class 2 Data (Note 3)
1
06, 07, 08
129
60
4
Class 3 Data (Note 3)
1
06, 07, 08
129
80
1
Internal Indications
2
00 (Note 4)
129
No object (cold restart command)
13
No object (warm restart command)
14
No object (delay measurement command) (Note 5)
23
For Notes, see the IMPLEMENTATION TABLE NOTES on the following page.