6-18
489 Generator Management Relay
GE Multilin
6.3 MODBUS MEMORY MAP
6 COMMUNICATIONS
6
DIGITAL INPUTS / GENERAL INPUT F
12B0
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
12B1
ASSERTED DIGITAL INPUT STATE
0 to 1
1
–
F131
0
12B2
INPUT NAME
0 to 12
1
–
F22
_
12B8
BLOCK INPUT FROM ONLINE
0 to 5000
1
s
F1
0
12B9
GENERAL INPUT F CONTROL
0 to 1
1
–
F105
0
12BA
PULSED CONTROL RELAY DWELL TIME
0 to 250
1
s
F2
0
12BB
ASSIGN CONTROL RELAYS (1-5)
0 to 4
1
–
F50
0
12BC
GENERAL INPUT F CONTROL EVENTS
0 to 1
1
–
F105
0
12BD
GENERAL INPUT F ALARM
0 to 2
1
–
F115
0
12BE
ASSIGN ALARM RELAYS (2-5)
1 to 4
1
–
F50
16
12BF
GENERAL INPUT F ALARM DELAY
1 to 50000
1
s
F2
50
12C0
GENERAL INPUT F ALARM EVENTS
0 to 1
1
–
F105
0
12C1
GENERAL INPUT F TRIP
0 to 2
1
–
F115
0
12C2
ASSIGN TRIP RELAYS (1-4)
0 to 3
1
–
F50
1
12C3
GENERAL INPUT F TRIP DELAY
1 to 50000
1
s
F2
50
DIGITAL INPUTS / GENERAL INPUT G
12D0
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
12D1
ASSERTED DIGITAL INPUT STATE
0 to 1
1
–
F131
0
12D2
INPUT NAME
0 to 12
1
–
F22
_
12D8
BLOCK INPUT FROM ONLINE
0 to 5000
1
s
F1
0
12D9
GENERAL INPUT G CONTROL
0 to 1
1
–
F105
0
12DA
PULSED CONTROL RELAY DWELL TIME
0 to 250
1
s
F2
0
12DB
ASSIGN CONTROL RELAYS (1-5)
0 to 4
1
–
F50
0
12DC
GENERAL INPUT G CONTROL EVENTS
0 to 1
1
–
F105
0
12DD
GENERAL INPUT G ALARM
0 to 2
1
–
F115
0
12DE
ASSIGN ALARM RELAYS (2-5)
1 to 4
1
–
F50
16
12DF
GENERAL INPUT G ALARM DELAY
1 to 50000
1
s
F2
50
12E0
GENERAL INPUT G ALARM EVENTS
0 to 1
1
–
F105
0
12E1
GENERAL INPUT G TRIP
0 to 2
1
–
F115
0
12E2
ASSIGN TRIP RELAYS (1-4)
0 to 3
1
–
F50
1
12E3
GENERAL INPUT G TRIP DELAY
1 to 50000
1
s
F2
50
DIGITAL INPUTS / REMOTE RESET
1300
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
DIGITAL INPUTS / TEST INPUT
1310
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
DIGITAL INPUTS / THERMAL RESET
1320
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
DIGITAL INPUTS / DUAL SETPOINTS
1340
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
1341
ACTIVE SETPOINT GROUP
0 to 1
1
–
F118
0
1342
EDIT SETPOINT GROUP
0 to 1
1
–
F118
0
DIGITAL INPUTS / SEQUENTIAL TRIP
1360
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
1361
SEQUENTIAL TRIP TYPE
0 to 1
1
–
F206
0
1362
ASSIGN TRIP RELAYS (1-4)
0 to 3
1
–
F50
1
1363
SEQUENTIAL TRIP LEVEL
2 to 99
1
× Rated MW
F14
5
1365
SEQUENTIAL TRIP DELAY
2 to 1200
1
s
F2
10
DIGITAL INPUTS / FIELD-BKR DISCREP.
1380
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
1381
FIELD STATUS CONTACT
0 to 1
1
–
F109
0
1382
ASSIGN TRIP RELAYS (1-4)
0 to 3
1
–
F50
1
1383
FIELD-BKR DISCREP. TRIP DELAY
1 to 5000
1
s
F2
10
DIGITAL INPUTS / TACHOMETER
13A0
ASSIGN DIGITAL INPUT
0 to 7
1
–
F210
0
13A1
RATED SPEED
100 to 3600
1
RPM
F1
3600
13A2
TACHOMETER ALARM
0 to 2
1
–
F115
0
13A3
ASSIGN ALARM RELAYS (2-5)
1 to 4
1
–
F50
16
13A4
TACHOMETER ALARM SPEED
101 to 175
1
%Rated
F1
110
13A5
TACHOMETER ALARM DELAY
1 to 250
1
s
F1
1
13A6
TACHOMETER ALARM EVENTS
0 to 1
1
–
F105
0
13A7
TACHOMETER TRIP
0 to 2
1
–
F115
0
13A8
ASSIGN TRIP RELAYS (1-4)
0 to 3
1
–
F50
1
13A9
TACHOMETER TRIP SPEED
101 to 175
1
%Rated
F1
110
13AA
TACHOMETER TRIP DELAY
1 to 250
1
s
F1
1
Table 6–1: 489 MEMORY MAP (SHEET 9 OF 24)
ADDR NAME
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3