8 phase differential trip accuracy, A) minimum pickup check, B) single infeed fault – GE 489 User Manual
Page 226: C) slope 1 check, D) slope 2 check, E) directional check, Phase differential trip accuracy -14

7-14
489 Generator Management Relay
GE Multilin
7.3 ADDITIONAL FUNCTIONAL TESTS
7 TESTING
7
7.3.8 PHASE DIFFERENTIAL TRIP ACCURACY
These tests will require a dual channel current source. The unit must be capable of injecting prefault cur-
rents and fault currents of a different value. Application of excessive currents (greater than 3
× CT) for
extended periods will cause damage to the relay.
a) MINIMUM PICKUP CHECK
1.
Connect the relay test set to inject Channel X current (I
x
) into the G3 terminal and out of H3 terminal (Phase A).
Increase I
x
until the differential element picks up. Record this value as pickup. Switch off the current. The theoretical
pickup can be computed as follows:
(EQ 7.5)
b) SINGLE INFEED FAULT
2.
Set the I
x
prefault current equal to 0. Set the fault current equal to CT. Apply the fault. Switch off the current. Record the
operating time.
3.
Set the I
x
prefault current equal to 0. Set the fault current equal to 5
× CT. Apply the fault. Switch off the current. Record
the operating time.
c) SLOPE 1 CHECK
4.
Connect the relay test set to inject Channel Y current (I
Y
) into the G6 terminal and out of H6 terminal. The angle
between I
x
and I
Y
will be 180°.
5.
Set pre-fault current, I
x
and I
Y
equal to zero.
6.
Set fault current, I
Y
equal to 1½ CT.
7.
At this value the relay should operate according to the following formula:
(EQ 7.6)
8.
Set fault current, I
x
equal to 0.95
× I
XOP1
. Apply the fault. The relay should operate. Switch off the current.
9.
Set fault current, I
x
equal to 1.05
× I
XOP1
. Apply the fault. The relay should restrain. Switch off the current.
d) SLOPE 2 CHECK
10. Set fault current, I
Y
equal to 2.5
× CT.
11. At this value the relay should operate according to the following formula.
(EQ 7.7)
12. Set fault current, I
x
equal to 0.95
× I
XOP2
. Switch on the test set. The relay should operate. Switch off the current.
13. Set fault current, I
x
equal to 1.05
× I
XOP2
. Switch on the test set. The relay should restrain. Switch off the current.
e) DIRECTIONAL CHECK
14. Set pre-fault current, I
x
and I
Y
equal to 2.5
× CT. At this value the conditions for CT saturation detection are set and the
relay will enable the directional check.
15. Set fault current, I
x
equal to 0.95
× I
XOP2
. Switch on the test set. The relay should restrain. Switch off the current.
16. Repeat Steps 1 through 15 for phases B and C.
NOTE
I
XPU
Pickup setting CT
×
=
I
XOP1
2 Slope 1 setting
–
2 Slope 1 setting
+
------------------------------------------------- 3 CT
Ч
2
-----------------
Ч
=
I
XOP2
2 Slope 1 setting
–
2 Slope 1 setting
+
------------------------------------------------- 2.5 CT
Ч
Ч
=