GE 489 User Manual
Page 191

GE Multilin
489 Generator Management Relay
6-29
6 COMMUNICATIONS
6.3 MODBUS MEMORY MAP
6
MONITORING / RUNNING HOUR SETUP
2AC0
INITIAL GEN. RUNNING HOUR
0 to 999999
1
h
F12
0
2AC2
GEN. RUNNING HOUR ALARM
0 to 2
1
–
F115
0
2AC3
ASSIGN ALARM RELAYS (2-5)
1 to 4
1
–
F50
16
2AC4
GEN. RUNNING HOUR LIMIT
1 to 1000000
1
h
F12
1000
2AC6
RESERVED
ANALOG I/O / ANALOG OUTPUT 1
2B00
ANALOG OUTPUT 1
0 to 42
1
–
F127
0
ANALOG I/O / ANALOG OUTPUT 2
2B01
ANALOG OUTPUT 2
0 to 42
1
–
F127
0
ANALOG I/O / ANALOG OUTPUT 3
2B02
ANALOG OUTPUT 3
0 to 42
1
–
F127
0
ANALOG I/O / ANALOG OUTPUT 4
2B03
ANALOG OUTPUT 4
0 to 42
1
–
F127
0
ANALOG I/O / ANALOG OUTPUTS
2B04
IA OUTPUT CURRENT MIN
0 to 2000
1
× FLA
F3
0
2B05
IA OUTPUT CURRENT MAX
0 to 2000
1
× FLA
F3
125
2B06
IB OUTPUT CURRENT MIN
0 to 2000
1
× FLA
F3
0
2B07
IB OUTPUT CURRENT MAX
0 to 2000
1
× FLA
F3
125
2B08
IC OUTPUT CURRENT MIN
0 to 2000
1
× FLA
F3
0
2B09
IC OUTPUT CURRENT MAX
0 to 2000
1
× FLA
F3
125
2B0A
AVG OUTPUT CURRENT MIN
0 to 2000
1
× FLA
F3
0
2B0B
AVG OUTPUT CURRENT MAX
0 to 2000
1
× FLA
F3
125
2B0C
NEG. SEQ. CURRENT MIN
0 to 2000
1
%FLA
F1
0
2B0D
NEG. SEQ. CURRENT MAX
0 to 2000
1
%FLA
F1
100
2B0E
AVERAGED GEN. LOAD MIN
0 to 2000
1
× FLA
F3
0
2B0F
AVERAGED GEN. LOAD MAX
0 to 2000
1
× FLA
F3
125
2B10
HOTTEST STATOR RTD MIN
–50 to 250
1
°C
F4
0
2B11
HOTTEST STATOR RTD MAX
–50 to 250
1
°C
F4
200
2B12
HOTTEST BEARING RTD MIN
–50 to 250
1
°C
F4
0
2B13
HOTTEST BEARING RTD MAX
–50 to 250
1
°C
F4
200
2B14
AMBIENT RTD MIN
–50 to 250
1
°C
F4
0
2B15
AMBIENT RTD MAX
–50 to 250
1
°C
F4
70
2B16
RTD #1 MIN
–50 to 250
1
°C
F4
0
2B17
RTD #1 MAX
–50 to 250
1
°C
F4
200
2B18
RTD #2 MIN
–50 to 250
1
°C
F4
0
2B19
RTD #2 MAX
–50 to 250
1
°C
F4
200
2B1A
RTD #3 MIN
–50 to 250
1
°C
F4
0
2B1B
RTD #3 MAX
–50 to 250
1
°C
F4
200
2B1C
RTD #4 MIN
–50 to 250
1
°C
F4
0
2B1D
RTD #4 MAX
–50 to 250
1
°C
F4
200
2B1E
RTD #5 MIN
–50 to 250
1
°C
F4
0
2B1F
RTD #5 MAX
–50 to 250
1
°C
F4
200
2B20
RTD #6 MIN
–50 to 250
1
°C
F4
0
2B21
RTD #6 MAX
–50 to 250
1
°C
F4
200
2B22
RTD #7 MIN
–50 to 250
1
°C
F4
0
2B23
RTD #7 MAX
–50 to 250
1
°C
F4
200
2B24
RTD #8 MIN
–50 to 250
1
°C
F4
0
2B25
RTD #8 MAX
–50 to 250
1
°C
F4
200
2B26
RTD #9 MIN
–50 to 250
1
°C
F4
0
2B27
RTD #9 MAX
–50 to 250
1
°C
F4
200
2B28
RTD #10 MIN
–50 to 250
1
°C
F4
0
2B29
RTD #10 MAX
–50 to 250
1
°C
F4
200
2B2A
RTD #11 MIN
–50 to 250
1
°C
F4
0
2B2B
RTD #11 MAX
–50 to 250
1
°C
F4
200
2B2C
RTD #12 MIN
–50 to 250
1
°C
F4
0
2B2D
RTD #12 MAX
–50 to 250
1
°C
F4
200
2B2E
AB VOLTAGE MIN
0 to 150
1
× Rated
F3
0
2B2F
AB VOLTAGE MAX
0 to 150
1
× Rated
F3
125
2B30
BC VOLTAGE MIN
0 to 150
1
× Rated
F3
0
2B31
BC VOLTAGE MAX
0 to 150
1
× Rated
F3
125
2B32
CA VOLTAGE MIN
0 to 150
1
× Rated
F3
0
2B33
CA VOLTAGE MAX
0 to 150
1
× Rated
F3
125
2B34
AVERAGE VOLTAGE MIN
0 to 150
1
× Rated
F3
0
2B35
AVERAGE VOLTAGE MAX
0 to 150
1
× Rated
F3
125
2B36
VOLTS/HERTZ MIN
0 to 200
1
× Rated
F3
0
Table 6–1: 489 MEMORY MAP (SHEET 20 OF 24)
ADDR NAME
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page 6–33