2 analog inputs 1 to 4, 2 analog inputs 1 to 4 -76, Table 4–8: analog output parameter – GE 489 User Manual
Page 126

4-76
489 Generator Management Relay
GE Multilin
4.12 S11 ANALOG I/O
4 SETPOINTS
4
4.12.2 ANALOG INPUTS 1 TO 4
PATH: SETPOINTS
ÖØ
S11 ANALOG I/O
ÖØ
ANALOG INPUT 1(4)
Table 4–8: ANALOG OUTPUT PARAMETER SELECTION
PARAMETER NAME
RANGE / UNITS
STEP
DEFAULT
MIN.
MAX
IA Output Current
0.00 to 20.00
× FLA
0.01
0.00
1.25
IB Output Current
0.00 to 20.00
× FLA
0.01
0.00
1.25
IC Output Current
0.00 to 20.00
× FLA
0.01
0.00
1.25
Avg. Output Current
0.00 to 20.00
× FLA
0.01
0.00
1.25
Neg. Seq. Current
0 to 2000% FLA
1
0
100
Averaged Gen. Load
0.00 to 20.00
× FLA
0.01
0.00
1.25
Hottest Stator RTD
–50 to +250°C or –58 to +482°F
1
0
200
Hottest Bearing RTD
–50 to +250°C or –58 to +482°F
1
0
200
Ambient RTD
–50 to +250°C or –58 to +482°F
1
–50
60
RTDs 1 to 12
–50 to +250°C or –58 to +482°F
1
–50
250
AB Voltage
0.00 to 1.50
× Rated
0.01
0.00
1.25
BC Voltage
0.00 to 1.50
× Rated
0.01
0.00
1.25
CA Voltage
0.00 to 1.50
× Rated
0.01
0.00
1.25
Volts/Hertz
0.00 to 2.00
× Rated
0.01
0.00
1.50
Frequency
0.00 to 90.00 Hz
0.01
59.00
61.00
Neutral Volt. (3rd)
0 to 25000 V
0.1
0.0
45.0
Average Voltage
0.00 to 1.50
× Rated
0.01
0.00
1.25
Power Factor
0.01 to 1.00 lead/lag
0.01
0.8 lag
0.8 lead
Reactive Power (Mvar)
–2.00 to 2.00
× Rated
0.01
0.00
1.25
Real Power
–2.00 to 2.00
× Rated
0.01
0.00
1.25
Apparent Power
0.00 to 2.00
× Rated
0.01
0.00
1.25
Analog Inputs 1 to 4
–50000 to +50000
1
0
50000
Tachometer
0 to 7200 RPM
1
3500
3700
Thermal Capacity Used
0 to 100%
1
0
100
Current Demand
0.00 to 20.00
× FLA
0.01
0.00
1.25
Mvar Demand
0.00 to 2.00
× Rated
0.01
0.00
1.25
MW Demand
0.00 to 2.00
× Rated
0.01
0.00
1.25
MVA Demand
0.00 to 2.00
× Rated
0.01
0.00
1.25
ANALOG INPUT 1
[ENTER] for more
ANALOG INPUT1:
Disabled
Range: Disabled, 4-20 mA, 0-20 mA, 0-1 mA
ANALOG INPUT1 NAME:
Analog I/P 1
Range: 12 alphanumeric characters
ANALOG INPUT1 UNITS:
Units
Range: 6 alphanumeric characters
ANALOG INPUT1
MINIMUM: 0
Range: –50000 to 50000 in steps of 1
ANALOG INPUT1
MAXIMUM: 100
Range: –50000 to 50000 in steps of 1
BLOCK ANALOG INPUT1
FROM ONLINE: 0 s
Range: 0 to 5000 sec. in steps of 1
ENTER
ESCAPE
р
р
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE