489 Generator Management Relay
GE Multilin
5.6 A5 EVENT RECORDER
5 ACTUAL VALUES
5
The 489 Event Recorder stores generator and system information each time an event occurs. The description of the event
is stored and a time and date stamp is also added to the record. This allows reconstruction of the sequence of events for
troubleshooting. Events include: all trips, any alarm optionally (except Service Alarm, and 489 Not Inserted Alarm, which
always records as events), loss of control power, application of control power, thermal resets, simulation, serial communica-
tion starts/stops and general input control functions optionally.
EVENT01
is the most recent event and
EVENT40
is the oldest event. Each new event bumps the other event records down
until the 40th event is reached. The 40th event record is lost when the next event occurs. This information can be cleared
using
S1 489 SETUP
ÖØ
CLEAR DATA
ÖØ
CLEAR EVENT RECORD
setpoint. The event record will not update if a digital input
programmed as Test Input is shorted.
ANALOG INPUT 2
EVENT01: 0.0 Units
Range: –50000 to 50000
Seen only if the Analog Input is in use.
ANALOG INPUT 3
EVENT01: 0.0 Units
Range: –50000 to 50000
Seen only if the Analog Input is in use.
ANALOG INPUT 4
EVENT01: 0.0 Units
Range: –50000 to 50000
Seen only if the Analog Input is in use.
Table 5–1: CAUSE OF EVENTS
TRIPS
Ambient RTD12 Trip *
Analog I/P 1 to 4 Trip *
Bearing RTD 7 Trip *
Bearing RTD 8 Trip *
Bearing RTD 9 Trip *
Bearing RTD 10 Trip *
Differential Trip
Distance Zone 1 Trip
Distance Zone 2 Trip
Field-Bkr Discr. Trip
Gnd Directional Trip
Ground O/C Trip
Hiset Phase O/C Trip
Input A to G Trip *
Loss of Excitation 1
Loss of Excitation 2
Low Fwd Power Trip
Neg Seq O/C Trip
Neutral O/V Trip
Neut. U/V (3rd) Trip
Offline O/C Trip
Overfrequency Trip
Overvoltage Trip
Phase O/C Trip
Phase Reversal Trip
Reactive Power Trip
Reverse Power Trip
RTD11 Trip *
Sequential Trip
Stator RTD 1 Trip *
Stator RTD 2 Trip *
Stator RTD 3 Trip *
Stator RTD 4 Trip *
Stator RTD 5 Trip *
Stator RTD 6 Trip *
Tachometer Trip
Thermal Model Trip
Underfrequency Trip
Undervoltage Trip
Volts/Hertz Trip
ALARMS (OPTIONAL EVENTS)
Ambient RTD12 Alarm *
Analog I/P 1 to 4 Alarm *
Bearing RTD 7 Alarm *
Bearing RTD 8 Alarm *
Bearing RTD 9 Alarm *
Bearing RTD 10 Alarm *
Breaker Failure
Current Demand Alarm
Gnd Directional Alarm
Ground O/C Alarm
Input A to G Alarm *
Low Fwd Power Alarm
MVA Alarm
Mvar Alarm
MW Alarm
NegSeq Current Alarm
Neut. U/V 3rd Alarm
Neutral O/V Alarm
Open RTD Alarm
Overcurrent Alarm
Overfrequency Alarm
Overvoltage Alarm
Reactive Power Alarm
Reverse Power Alarm
RTD11 Alarm *
Short/Low RTD Alarm
Stator RTD 1 Alarm
Stator RTD 2 Alarm
Stator RTD 3 Alarm
Stator RTD 4 Alarm
Stator RTD 5 Alarm
Stator RTD 6 Alarm
Tachometer Alarm
Thermal Model Alarm
Trip Coil Monitor
Trip Counter Alarm
Underfrequency Alarm
Undervoltage Alarm
VT Fuse Fail Alarm
OTHER
489 Not Inserted
Control Power Applied
Control Power Lost
Dig I/P Waveform Trig
Input A to G Control *
IRIG-B Failure
Serial Comm. Start
Serial Comm. Stop
Serial Waveform Trip
Setpoint 1 Active
Setpoint 2 Active
Simulation Started
Simulation Stopped
Thermal Reset Close
Thermal Reset Open
*
reflects the name that is programmed
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE