Table 6–2: data formats (sheet 4 of 5) – GE 489 User Manual
Page 199

GE Multilin
489 Generator Management Relay
6-37
6 COMMUNICATIONS
6.3 MODBUS MEMORY MAP
6
F139
Unsigned
16 bit integer
Force operation of relays
F140
16 bits
General Status
F141
16 bits
Output Relay Status
F142
Unsigned
16 bit integer
Thermal Model curve style selection
0 = Standard, 1 = Custom, 2 = Voltage Dependent
F200
Unsigned
16 bit integer
Comm. monitor buffer status
F201
Unsigned
16 bit integer
Curve Reset Type
0 = Instantaneous, 1 = Linear
F202
Unsigned
16 bit integer
Inadvertent energization arming type
0 = U/V and Offline, 1 = U/V or Offline
F206
Unsigned
16 bit integer
Sequential trip type
0 = Low Forward Power, 1 = Reverse Power
F207
Unsigned
16 bit integer
Switch status
0 = Open, 1 = Shorted
F208
Unsigned
16 bit integer
Undervoltage trip element type
0 = Curve, 1 = Definite Time
F209
Unsigned
16 bit integer
Breaker operation type
0 = Breaker Auxiliary a, 1 = Breaker Auxiliary b
F210
Unsigned
16 bit integer
Assignable input selection
Table 6–2: DATA FORMATS (SHEET 4 OF 5)
FORMAT
CODE
TYPE
DEFINITION
VALUE
PARAMETER
VALUE PARAMETER
0
Disabled
5
R5 Alarm
1
R1 Trip
6
R6 Service
2
R2 Auxiliary
7
All Relays
3
R3 Auxiliary
8
No Relays
4
R4 Auxiliary
BIT NO.
PARAMETER
BIT NO.
PARAMETER
Bit 0
Relay in Service
Bit 8
Breaker Open LED
Bit 1
Active Trip Condition
Bit 9
Breaker Closed LED
Bit 2
Active Alarm Condition
Bit 10
Hot Stator LED
Bit 3
Reserved
Bit 11
Neg. Sequence LED
Bit 4
Reserved
Bit 12
Ground LED
Bit 5
Reserved
Bit 13
Loss of Field LED
Bit 6
Reserved
Bit 14
VT Failure LED
Bit 7
Simulation Mode Enabled
Bit 15
Breaker Failure LED
BIT NO.
PARAMETER
BIT NO.
PARAMETER
Bit 0
R1 Trip
Bit 8
Reserved
Bit 1
R2 Auxiliary
Bit 9
Reserved
Bit 2
R3 Auxiliary
Bit 10
Reserved
Bit 3
R4 Auxiliary
Bit 11
Reserved
Bit 4
R5 Alarm
Bit 12
Reserved
Bit 5
R6 Service
Bit 13
Reserved
Bit 6
Reserved
Bit 14
Reserved
Bit 7
Reserved
Bit 15
Reserved
VALUE
PARAMETER
VALUE
PARAMETER
0
Buffer Cleared
4
Illegal Count
1
Received OK
5
Illegal Reg. Addr.
2
Wrong Slave Addr.
6
CRC Error
3
Illegal Function
7
Illegal Data
VALUE
PARAMETER
VALUE
PARAMETER
0
None
4
Input 4
1
Input 1
5
Input 5
2
Input 2
6
Input 6
3
Input 3
7
Input 7