beautypg.com

3 installation specifications, 1 primequest 1800e2 installation specifications – FUJITSU PRIMEQUEST 1000 Series C122-E119EN User Manual

Page 26

background image

1.3

Installation Specifications

This section lists the installation specifications of each device.

-

1.3.1 PRIMEQUEST 1800E2 installation specifications

-

1.3.2 PRIMEQUEST 1800E installation specifications

-

1.3.3 PCI_Box installation specifications

1.3.1

PRIMEQUEST 1800E2 installation specifications

TABLE 1.2 PRIMEQUEST 1800E2 installation specifications

Item

Description

External

dimensions

[mm (in.)]

Width

482 (18.98)

Depth (*1)

800 (31.50)

Height

530 (20.87)

Weight [kg (lb)] (*2)

150 (330)

Air conditioning

requirements

Maximum heat output [kJ/h (BTU/h)]

14,400 (13,649)

Exhaust air

flow [m

3

/min

(ft

3

/min)] (*3)

FAN at low speed (Low)

14 (494)

FAN at normal speed (Normal)

21 (742)

FAN at high speed (High)

24 (848)

Temperature

and humidity

requirements

(*4)

Operating

Temperature [°C (°F)]

(*5)

Humidity [%RH]

20 to 80

Maximum wet-bulb

temperature [°C (°F)]

29 (84.2)

Non-operating (*6) Temperature [°C (°F)]

0 to 50 (32 to 122)

Humidity [%RH]

8 to 80

Maximum wet-bulb

temperature [°C (°F)]

29 (84.2)

Noise [dB] (*7) (*8)

61

Acoustic power level [B] (*8)

7.8

Allowable

vibration [m/

s

2

(gal)]

Operating (including standby state)

4.0 (400) (synthetic seismic

waves)

Non-operating (*9)

10.0 (1000) (synthetic

seismic waves)

Allowable dust concentration [mg/m

3

]

0.15

Power

requirements

Input voltage and number of phases

200 to 240 VAC ±10%

Frequency and fluctuation range

50/60 Hz +2/-4%

PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information

6

C122-H004-07EN