Install the HP Model 30/FC High Availability Disk Array

1. Check Power Requirements

Refer to the disk array DC power requirements in the Reference chapter of the Hewlett-Packard Model 30/FC High
Availability Disk Array Service Manual
(part number A3661-90002) to make sure the installation site meets these
requirements.

The HP Model 30/FC High Availability Disk Array uses 200VAC to 240VAC nominal; 110VAC is not supported. One
power distribution unit (PDU) in the cabinet can provide sufficient power for one, two, or three disk arrays. The disk
array and HP FC-AL hub are connected to the PDU; the PDU is connected to an UPS.

Make sure the UPS is capable of supplying an amount of power equal to the sum of the VA units required to power all
the systems and peripherals installed in the cabinet.

Consider the type of PDU that is required. PDUs have power inlets and outlets that impinge on clearances necessary to
fully open the disk array’s fan pack door. Table 1 specifies the required PDUs for various hardware configurations
installed in one cabinet.

Table 1 – PDU Requirements

PDU part
number

PDU product
number

Description

Typical application

Racking restrictions

E5929-63001

E5929A

- Universal PDU
- Ten C-13 and one C-19

outlets

- One C-20 inlet for

detachable cords

C-19 outlet is for SPUs
requiring a 20-amp
connector.
C-20 inlet facilitates a
universal set of
detachable power cords.
Typically, for external
UPS applications

Must be racked on rails at or
above 4 EIAs to clear the
C-19 outlet.
If the C-19 outlet is not
used, must be racked on
rails at or above 1 EIA to
clear the C-20 inlet.

E5931A

- N. America 220 V PDU
- Ten C-13 outlets
- Attached 3 m power

cord with L6-30P plug

Attached to a 3.0 or 5.5
kva N. American UPS

None

E5932A

- Europe 220 PDU
- Ten C-13 outlets
- Attached 3 m power

cord without plug

Attached to a 3.0 or 5.5
kva European UPS

None

E4456-63001

E4456B

- N. America 220 V PDU
- Ten C-13 and one C-19

outlets

- Attached power cord

with L6-20P plug

C-19 outlet is for SPUs
requiring a 20-amp
connector.
Power cord typical for
N. America wall outlet
connection.

Must be racked on rails at or
above 4 EIAs to clear the
C-19 outlet.
If the C-19 outlet is not
used, must be racked on the
bottom of the rack without
rails.

E4457-63001

E4457B

- Europe 220 V PDU
- Ten C-13 and one C-19

outlets

- Attached power cord

without a plug

C-19 outlet is for SPUs
requiring a 20-amp
connector.
Power cord has stripped
ends for attaching
localized plug.

Must be racked on rails at or
above 4 EIAs to clear the
C-19 outlet.
If the C-19 outlet is not
used, can be racked on the
bottom of the rack without
rails.

C2786-63006

E4456A

- N. America

220 V PDU

- Ten C-13 outlets
- Attached power cord

with L6-20P plug

None

C2786-63007

E4457A

- Europe 220 V PDU
- Ten C-13 outlets
- Attached power cord

without plug

Power cord has stripped
ends for attaching
localized plug.

None