C_SE_NA and C_SE_NB
The Control Normalized Value Set Point Command information object and the
Control Scaled Value Set Point Command information object use one word with
word addressing. For example, if you configured the following points:
The following table describes how these points would be used.
Inf. Object Address
Module Database Address
1100
Word 2000 (Word address 2000)
400
Word 10 (Word address 10. Must match the
configuration of point 400 in M_ME_NA.)
1101
Word 2001 (Word address 2001)
401
Word 12 (Word address 12. Must match the
configuration of point 401 in M_ME_NA.)
1102
Word 2002 (Word address 2002)
402
Word 18 (Word address 18. Must match the
configuration of point 402 in M_ME_NA.)
The Control Normalized Measured information objects use a data representation
defined by the protocol specification to represent fractional decimal values. The
following table describes the value for each bit as a reciprocal power of two (2),
that is two (2) raised to the power of a negative exponent (-1 through -15). Bit 15
is the Sign Bit.
Bit
15
14
13
12
11
10
9
8
7 6 5 4 3 2 1 0
Value
Hex(h)
Decimal
Sign 4000h
2
-1
2000h
2
-2
1000h
2
-3
800
h
2
-4
400
h
2
-5
200
h
2
-6
100
h
2
-7
80
h
2
-8
40
h
2
-9
20
h
2
-10
10
h
2
-11
8h
2
-12
4h
2
-13
2h
2
-14
1h
2
-15
4000h
0.5
0 1
0
0
0 0 0 0 0 0 0 0 0 0 0 0
2000h
0.25
0 0
1
0
0 0 0 0 0 0 0 0 0 0 0 0
1000h
0.125
0 0
0
1
0 0 0 0 0 0 0 0 0 0 0 0
6000h
0.75
0 1
1
0
0 0 0 0 0 0 0 0 0 0 0 0
3210h
0.395751953125
0 0
1
1
0 0 1 0 0 0 0 1 0 0 0 0