2.9 [M_ME_NC_1]

This section defines the monitored short-float point database. This information is

sourced from the database and is transferred to the remote Master unit.
To determine the IOA (Information Object Address) for each object, add the

P

OINT

#

in the following section to the value of the M_ME_NC Parameter Offset

parameter set in the previous section.
This section takes the following parameters:

P

OINT

#

DB

ADDRESS

G

ROUPS

(page 50)

D

EFAULT

D

EADBAND

IV

DB

B

IT

Each point consumes four 8-bit bytes (two 16-bit words). The

DB

A

DDRESS

value

corresponds to the double-word offset address in the database.
The

DB

ADDRESS

should be located in a database area that is being constantly

moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference

chapter of this manual.

2.10 [M_IT_NA_1]

This section defines the monitored integrated totals (counter) database. This

information is sourced from the database and is transferred to the remote Master

unit. This section takes the following parameters:

P

OINT

#

DB

ADDRESS

G

ROUPS

(page 50)

IV

DB

B

IT

Each point consumes four 8-bit bytes (two 16-bit words). The

DB

A

DDRESS

value

corresponds to the double-word offset address in the database.
The

DB

ADDRESS

should be located in a database area that is being constantly

moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference

chapter of this manual.