2.9 [M_ME_NC_1]
This section defines the monitored short-float point database. This information is
sourced from the database and is transferred to the remote Master unit.
To determine the IOA (Information Object Address) for each object, add the
P
OINT
#
in the following section to the value of the M_ME_NC Parameter Offset
parameter set in the previous section.
This section takes the following parameters:
P
OINT
#
DB
ADDRESS
G
ROUPS
(page 50)
D
EFAULT
D
EADBAND
IV
DB
B
IT
Each point consumes four 8-bit bytes (two 16-bit words). The
DB
A
DDRESS
value
corresponds to the double-word offset address in the database.
The
DB
ADDRESS
should be located in a database area that is being constantly
moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.
2.10 [M_IT_NA_1]
This section defines the monitored integrated totals (counter) database. This
information is sourced from the database and is transferred to the remote Master
unit. This section takes the following parameters:
P
OINT
#
DB
ADDRESS
G
ROUPS
(page 50)
IV
DB
B
IT
Each point consumes four 8-bit bytes (two 16-bit words). The
DB
A
DDRESS
value
corresponds to the double-word offset address in the database.
The
DB
ADDRESS
should be located in a database area that is being constantly
moved from the gateway to the Master.
For additional information on how to set these parameters, see the Reference
chapter of this manual.