ProSoft Technology 5201-MNET-101S User Manual
Page 101

IEC-101 Slave ♦ ProLinx Communication Gateway
Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 101 of 159
August 6, 2010
A network Master may also dynamically change the deadband for each
monitored point. The Master may send one of the following commands:
Type
Command
110
Parameter of Measured Normalized Data (M_ME_NA)
111
Parameter of Measured Scaled Data (M_ME_NB)
112
Parameter of Measured Short Floating Point (M_ME_NC)
The protocol specification explains that the qualifier value for these commands
should be configured as:
Bits
Value
Description
1 to 6
0
Not Used
1
Threshold Value (Deadband)
2
Smoothing Factor (filter time constant) - Not Supported
3
Low Limit Transmission of Measured Value
4
High Limit Transmission of Measured Value
5..31
Reserved
7
0
No Change
1
Change
8
0
Operation
1
Not in Operation
The gateway calculates the Low Limit and High Limit values using the formula
below (so these values cannot be changed dynamically)
Low Limit = (LAST REPORTED VALUE) - Deadband
High Limit = (LAST REPORTED VALUE) + Deadband
These commands must be sent to a specific Information Object Address. The
gateway associates each monitor measured point with a parameter point through
the following configuration parameters: