beautypg.com

Configuration – ProSoft Technology 5201-MNET-101S User Manual

Page 114

background image

Reference

IEC-101 Slave ♦ ProLinx Communication Gateway

Protocol Manual

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Page 114 of 159

ProSoft Technology, Inc.

August 6, 2010

Configuration
In order to configure the ProLinx gateway to use the Command Block

functionality (if present on your specific gateway model), there are two

parameters to be configured, DB Input Window Start and DB Output Window

Start, as seen below.

Note: If the PCB configuration for your specific gateway model does not include the window shown

above, it means your model does not support Command Block functionality.


The DB Input Window Start parameter defines the ProLinx database starting

register where the command block request data should be placed (transferred

from the remote node to the ProLinx gateway). In the example above, a Modbus

TCP/IP client would send a control block request to the ProLinx gateway starting

at database start register 3000. A value of -1 in this parameter disables this

functionality.
The DB Output Window Start parameter defines the ProLinx database starting

register where the control block response should be placed (transferred from the

ProLinx gateway to the remote node.) After receiving a command from a remote

node, some control block requests require a response be returned from the

gateway (for example, the control block to retrieve the current time from the

gateway). For the example above, the remote node must read the control block

response from the ProLinx gateway starting at database start register 3100. A

value of -1 in this parameter disables this functionality.