Process information in control direction – ProSoft Technology 5201-MNET-101S User Manual
Page 133

IEC-101 Slave ♦ ProLinx Communication Gateway
IEC 60870-5-101 Slave Interoperability Statement
IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 133 of 159
August 6, 2010
<34> := Measured value, normalized value with time tag
CP56Time2a
M_ME_TD_1
<35> := Measured value, scaled value with time tag
CP56Time2a
M_ME_TE_1
<36> := Measured value, short floating-point value
with time tag CP56Time2a
M_ME_TF_1
<37> := Integrated totals with time tag CP56Time2a
M_IT_TB_1
<38> := Event of protection equipment with time tag
CP56Time2a
M_EP_TD_1
<39> := Packed start events of protection equipment
with time tag CP56time2a
M_EP_TE_1
<40> := Packed output circuit information of protection
equipment with time tag CP56Time2a
M_EP_TF_1
6.6.2 Process Information in Control Direction
(Station-specific parameter; mark each Type ID "
X" if it is only used in the
standard direction, "
R" if only used in the reverse direction, and "B" if used in
both directions)
<45> := Single command
C_SC_NA_1
<46> := Double command
C_DC_NA_1
<47> := Regulating step command
C_RC_NA_1
<48> := Set point command, normalized value
C_SE_NA_1
<49> := Set point command, scaled value
C_SE_NB_1
<50> := Set point command, short floating-point value C_SE_NC_1
<51> := Bitstring of 32 bit
C_BO_NA_1
<58> := Single command with time tag CP56Time2a
C_SC_TA_1
<59> := Double command with time tag CP56Time2a
C_DC_TA_1
<60> := Regulating step command with time tag
CP56Time2a
C_RC_TA_1
<61> := Set point command, normalized value
with time tag CP56Time2a
C_SE_TA_1
<62> := Set point command, scaled value
with time tag CP56Time2a
C_SE_TB_1
<63> := Set point command, short floating-point value
with time tag CP56Time2a
C_SE_TC_1
<64> := Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_1
Either the ASDUs of the set <45>-<51> or of the set <58>-<64> are used.