Example 1 - command request without response only, Command request block, Command response block – ProSoft Technology 5201-MNET-101S User Manual
Page 117

IEC-101 Slave ♦ ProLinx Communication Gateway
Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 117 of 159
August 6, 2010
Example 1 - Command Request Without Response only
For this example, the remote node is passing a timestamp event to be
transferred to the remote client connected to the ProLinx gateway.
The following block can be used for the first request.
Command Request Block
Word
Offset
Database
Address
Value
Description
0
3000
100
Block ID1 - Command Request Without Response
1
3001
0
Block ID2 - Command Request With Response. Move
a value of 0 or any other value out of the 200 to 203
range since no data is requested back from the
gateway
2 to 10
3002 to 3010 Event Data
Timestamp event
99
3099
100
Block ID1 - Command Request Without Response
Command Response Block
Word Offset Database
Address
Value
Description
0
3100
0
Block ID2 - Command Request With Response.
1
3101
100
Block ID1 - Command Request Without Response
2 to 98
3102 to 3198 Reserved
Reserved - no update
99
3199
0
Block ID2 - Command Request With Response.
In order to send another command request to pass another event, use the
following format:
Command Request Block
Word
Offset
Database
Address
Value
Description
0
3000
101
Block ID1 - Command Request Without Response
1
3001
0
Block ID2 - Command Request With Response. Move
a value of 0 or any other value out of the 200 to 203
range since no data is requested back from the
gateway
2 to 10
3002 to 3010 Event Data
Timestamp event
99
3099
101
Block ID1 - Command Request Without Response