Control points addressing – ProSoft Technology 5201-MNET-101S User Manual
Page 93
IEC-101 Slave ♦ ProLinx Communication Gateway
Reference
IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 93 of 159
August 6, 2010
Control Points Addressing
Control points must be configured in a database area that is updated in the
gateway. You must associate each point to a database address in the 101S
gateway. The interpretation of the DB Address parameter in the configuration
tables depends on the point type configured and the type of addressing
associated with that point type.
ASDU Type
Data Size
Addressing Type
C_SC_NA
1 bit
Bit
C_DC_NA
2 bits
Bit
C_RC_NA
1 byte
Byte
C_BO_NA
2 words
Double word
C_SE_NA
1 word
Word
C_SE_NB
1 word
Word
C_SE_NC
2 words
Double word