101S Protocol Configuration
IEC-101 Slave ♦ ProLinx Communication Gateway
Protocol Manual
IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 28 of 159
ProSoft Technology, Inc.
August 6, 2010
Example I - Freeze Start Type
If the gateway should send the counter points on the hourly turn around time and
also 45 minutes later, the Mode A parameters should be configured as follows:
So the gateway would send events as follows (Hours:Minutes:Seconds):
17:00:00
17:45:00
18:00:00
18:45:00
19:00:00
19:45:00
…
The following illustration shows a typical communication example when the Mode
A is selected during unbalanced mode operation: