Interval for freeze – ProSoft Technology 5201-MNET-101S User Manual

Page 29

background image

IEC-101 Slave ♦ ProLinx Communication Gateway

101S Protocol Configuration

IEC 60870-5-101 v3 Slave (Firmware version 3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 29 of 159

August 6, 2010

Example II - Freeze Start Type
If the gateway powers up with the following date and time settings on its internal

clock:

03/25/2004 18:07:42

And if you configure the Interval For Freeze parameter to 15 seconds, as follows:

The Freeze Start Type parameter determines when the gateway will begin

sending these messages, as follows:

If the Freeze Start Type is set to: Then Messages will start being sent at:
D

03/26/2004 00:00:00 and every 15 seconds thereafter

H

03/25/2004 19:00:00 and every 15 seconds thereafter

M

03/25/2004 18:08:00 and every 15 seconds thereafter

Once message transmission begins, the gateway will freeze and transmit counter

values at whatever interval has been configured using the Interval For Freeze

parameter. In this example, that would be every 15-seconds.

2.1.18 Interval for Freeze

0 to 65535

seconds

Freeze Start Type and Interval for Freeze are used if Mode A operation is to be

used for the counter freeze operation. If they are not used, the gateway will

operate in Mode D.