Delay Preset
This parameter sets an interval for each Data Map copy operation. The value you

put for the Delay Preset is not a fixed amount of time. It is the number of firmware

scans that must transpire between copy operations.
The firmware scan cycle can take a variable amount of time, depending on the

level of activity of the protocol drivers running on the ProLinx gateway and the

level of activity on the gateway's communication ports. Each firmware scan can

take from 1 to several milliseconds to complete. Therefore, Data Map copy

operations cannot be expected to happen at regular intervals.
If multiple copy operations (several rows in the Data map section) happen too

frequently or all happen in the same update interval, they could delay the process

scan of the gateway protocols, which could result in slow data updates or missed

data on communication ports. To avoid these potential problems, you should set

the Delay Preset to different values for each row in the Data Map section and set

them to higher, rather than lower, numbers.
For example, Delay Preset values below 1000 could begin to cause a noticeable

delay in data updates through the communication ports. And you should not set

all Delay Presets to the same value. Instead, use different values for each row in

the Data Map such as 1000, 1001, and 1002 or any other different Delay Preset

values you like. This will prevent the copies from happening concurrently and

prevent possible process scan delays.