ProSoft Technology MVI56E-MCM/MCMXT User Manual
Page 60

Configuration as a Modbus Slave
MVI56E-MCM ♦ ControlLogix Platform
User Manual
Modbus Communication Module
Page 60 of 199
ProSoft Technology, Inc.
June 18, 2014
MVI Address
0xxx
1xxxx
3xxxx
4xxxx
Tag Address
50
0801 to 0816
10801 to 10816 30051
40051
WriteData[50]
100
1601 to 1616
11601 to 11616 30101
40101
WriteData[100]
200
3201 to 3216
13201 to 13216 30201
40201
WriteData[200]
500
8001 to 8016
18001 to 18016 30501
40501
WriteData[500]
598
9569 to 9584
19569 to 19584 30599
40599
WriteData[598]
599
9585 to 9600
19585 to 19600 30600
40600
WriteData[599]
600 to 999
N/A
N/A
N/A
N/A
Reserved
1000
31001*
41001
ReadData[0]
1001
31002*
41002
ReadData[1]
1002
31003*
41003
ReadData[2]
1003
31004*
41004
ReadData[3]
1004
31005*
41005
ReadData[4]
1005
31006*
41006
ReadData[5]
1006
31007*
41007
ReadData[6]
1007
31008*
41008
ReadData[7]
1008
31009*
41009
ReadData[8]
1009
31010*
41010
ReadData[9]
1010
31011*
41011
ReadData[10]
1050
31051*
41051
ReadData[50]
1100
31101*
41101
ReadData[100]
1200
31201*
41201
ReadData[200]
1500
31501*
41501
ReadData[500]
1598
31599*
41599
ReadData[598]
1599
31600*
41600
ReadData[599]
The above addressing chart will work with many Modbus applications. Values
listed in the R
EAD
D
ATA
array for 31001 to 31600 are shown with an * beside
them.
Although these are valid addresses, they will not work in the application. The
Master must issue a Write command to the addresses that correspond to the
R
EAD
D
ATA
array. For Modbus addresses 3xxxx these are considered Input
registers, and a Modbus Master does not have a function code for this type of
data.