MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 12 of 199

ProSoft Technology, Inc.

June 18, 2014

1.3

Package Contents

The following components are included with your MVI56E-MCM module, and are
all required for installation and configuration.

Important: Before beginning the installation, please verify that all of the following items are

present.

Qty.

Part Name

Part Number

Part Description

1

MVI56E-MCM Module MVI56E-MCM

Modbus Communication Module

1

Cable

RL-CBL025

5 foot Ethernet Straight-Through Cable
(Gray)

2

Cable

Cable #14, RJ45 to
DB9 Male Adapter
cable

For DB9 Connection to Module’s
Application Serial Port

2

Adapter

1454-9F

Two Adapters, DB9 Female to Screw
Terminal. For RS422 or RS485
Connections to Port 1 and 2 of the Module

1

ProSoft Solutions
DVD

DVD-001

Contains ProSoft Configuration Builder
(PCB) and ProSoft Discovery Service (PDS)
for the MVI56E-MCM modules.

If any of these components are missing, please contact ProSoft Technology
Support for replacement parts.

1.4

Setting Jumpers

There are three jumpers located at the bottom of the module. The first two
jumpers (P1 and P2) set the serial communication mode: RS-232, RS-422 or RS-
485.

The following illustration shows the MVI56E-MCM jumper configuration, with the
Setup Jumper OFF.

The Setup Jumper acts as "write protection" for the module’s firmware. In "write
protected" mode, the Setup pins are not connected, and the module’s firmware
cannot be overwritten. The module is shipped with the Setup jumper OFF. If you
need to update the firmware, apply the Setup jumper to both pins.