ProSoft Technology MVI56E-MCM/MCMXT User Manual
Page 133
MVI56E-MCM ♦ ControlLogix Platform
Reference
Modbus Communication Module
User Manual
ProSoft Technology, Inc.
Page 133 of 199
June 18, 2014
Error Code Description
0
No error, transfer successful
-1
Error transferring general configuration information.
-2
Error transferring Modbus Port 1 Master command list
-3
Error transferring Modbus Port 2 Master command list
Ladder logic must handle the 9997 command. No ladder logic is required for the
warm or cold boot commands.
Write Configuration Block (-9000 and -6000 to -6003 or -6100 to -6103)
This special function is used to update the processor's module configuration
information when the module’s configuration has been altered by a remote
Master. The remote Master writes a block code 9997 to module register 15400
(Modbus Address 55401), causing the module to write its current configuration to
the processor. Ladder logic must handle the receipt of these blocks.
The first write block from the module contains a value of -9000 in the first word.
Block Response from Module to Processor
Word Offset
Description
Length
0
Reserved
1
1
-9000
1
2 to 7
Backplane Setup
6
8 to 32
Port 1 Configuration
25
33 to 57
Port 2 Configuration
25
58 to 60
Port 1 Configuration (continued)
3
61 to 63
Port 2 Configuration (continued)
3
64 to 248
Spare
185
249
-9000
1
Blocks -6000 to -6012 and -6100 to -6112 contain the Master Command List
Data for ports 1 and 2, respectively:
Block Response from Module to Processor
Word Offset
Description
Length
0
Reserved
1
1
-6000 to -6012 and -6100 to -6112
1
2 to 9
Command Definition
8
10 to 17
Command Definition
8
18 to 25
Command Definition
8
26 to 33
Command Definition
8
34 to 41
Command Definition
8
42 to 49
Command Definition
8