MVI56E-MCM ♦ ControlLogix Platform
Start Here
Modbus Communication Module
User Manual
ProSoft Technology, Inc.
Page 21 of 199
June 18, 2014
5 If you are using the module in a different slot (or remote rack), edit the
connection input and output variables that define the path to the module. Edit
the text in the F
INAL
N
AME
column (N
AME
column for controller revision 16 or
less). For example, if your module is located in slot 3, change Local:1:I in the
above picture to Local:3:I. Do the same for Local:1:O. If your module is
located in Slot 1 of the local rack, this step is not required.
6 Click OK
to confirm the import. RSLogix will indicate that the import is in
progress:
When the import is completed, the new rung with the Add-On Instruction will
be visible as shown in the following illustration.
The procedure has also imported new User Defined Data Types, Controller
Tags, and the Add-On Instruction for your project.
7 Save the application and then download the sample ladder logic into the
processor.