beautypg.com

ProSoft Technology MVI56E-MCM/MCMXT User Manual

Page 141

background image

MVI56E-MCM ♦ ControlLogix Platform

Reference

Modbus Communication Module

User Manual

ProSoft Technology, Inc.

Page 141 of 199

June 18, 2014

RS-232: Null Modem Connection (Hardware Handshaking)

This type of connection is used when the device connected to the module
requires hardware handshaking (control and monitoring of modem signal lines).

RS-232: Null Modem Connection (No Hardware Handshaking)

This type of connection can be used to connect the module to a computer or field
device communication port.

Note: For most null modem connections where hardware handshaking is not required, the Use
CTS Line
parameter should be set to N

and no jumper will be required between Pins 7 (RTS) and 8

(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is

required between the RTS and the CTS lines on the port connection.