Reference

MVI56E-MCM ♦ ControlLogix Platform

User Manual

Modbus Communication Module

Page 124 of 199

ProSoft Technology, Inc.

June 18, 2014

The following table describes the format of these blocks.

Block Request from Processor to Module

Word Offset

Description

Length

0

3002 to 3003 or 3102 to 3103

1

1 to 247

Spare

246

The module will recognize the request by receiving the special write block code
and respond with a read block with the following format:

Block Response from Module to Processor

Word Offset

Description

Length

0

Reserved

1

1

Write Block ID

1

2 to 129

Slave Poll Status Data

128

130 to 248

Spare

119

249

3002 to 3003 or 3102 to 3103

1

Ladder logic can be written to override the value in the Slave status table. It can
disable (state value of 3) by sending a special block of data from the processor to
the Slave. Port 1 Slaves are disabled using block 3000, and Port 2 Slaves are
disabled using block 3100. Each block contains the Slave node addresses to
disable. The following table describes the structure of the block.

Block Request from Processor to Module

Word Offset

Description

Length

0

3000 or 3100

1

1

Number of Slaves in Block

1

2 to 201

Slave indexes

200

202 to 247

Spare

46

The module will respond with a block with the same identification code received
and indicate the number of Slaves acted on with the block. The following table
describes the format of the response block.

Block Response from Module to Processor

Word Offset

Description

Length

0

Reserved

1

1

Write Block ID

1

2

Number of Slaves processed

1

3 to 248

Spare

246

249

3000 or 3100

1