1.6.5 Adjust the Input and Output Array Sizes (Optional)

The module internal database is divided into two user-configurable areas:
 Read Data
 Write Data.
The Read Data area is moved from the module to the processor, while the Write
Data area is moved from the processor to the module. You can configure the
start register and size of each area. The size of each area you configure must
match the Add-On Instruction controller tag array sizes for the R

EAD

D

ATA

and

W

RITE

D

ATA

arrays.

The MVI56E-MCM sample program is configured for 600 registers of R

EAD

D

ATA

and 600 registers of W

RITE

D

ATA

,

which is sufficient for most application. This

topic describes how to configure user data for applications requiring more than
600 registers of ReadData and WriteData. In this example, we will expand both
the Read and Write Data sizes to 1000.

Important: Because the module pages data in blocks of 200 registers at a time, you must
configure your user data in multiples of 200 registers.

Caution: When you change the array size, RSLogix may reset the MCM tag values to zero. To

avoid data loss, be sure to save your settings before continuing.

1 In the C

ONTROLLER

O

RGANIZATION

window, expand the D

ATA

T

YPES

and

U

SER

-D

EFINED

folders, and then double-click MCMDATA.

This action opens

an edit window for the MCMDATA data type.

2 In the edit window, change the value of the R

EAD

D

ATA

array from INT[600] to

INT[1000] as shown, and then click A

PPLY

.

Note: If RSLogix resets your data values, refer to the backup copy of your program to re-enter your
configuration parameters.

3 Next, navigate to C

ONTROLLER

T

AGS

and double click to open an edit

window. Click the M

ONITOR

T

AGS

tab at the bottom of the edit window.