beautypg.com

ProSoft Technology 3170-PDP User Manual

Page 62

background image

3170-PDP ♦ FLEX Platform

Configure the Adapter for Master/Slave Communication

FLEX I/O™ PROFIBUS Adapter

Page 62 of 152

ProSoft Technology, Inc.

August 23, 2007

User Parameter Message, Full Format

Name Value

Description

Octet 51:

00h

Slot 8 all sizes zero

Octet 52 to 244:

00h

Not used

1

In your network, double-click on the slave icon.
You see the 3170-PDP Device Parameters screen

Double-click on

You see the User Parameter Data screen:

2

Enter the Full Format data values as shown in the User Parameter example:

User Parameter Example

User Parameter Message, Full Format (Length 43 bytes)

Name Value

Description

Octet 8

00h

Reserved

Octet 9:

0Bh

Full Format, Use safe state

Octet 10 to 11:

0281h

Slot 1 Module Key 1794-IB16 16-point discrete input module

Octet 12:

10h

Slot 1 config size 1 word, safe state size 0 words

Octet 13 to 14:

0000h

1 config word, input delay times

Octet 15 to 16:

0191h

Slot 2 Module Key 1794-OB16 16-point discrete output
module

Octet 17:

01h

Slot 2 config size 0 words, safe state size 1 word

Octet 18 to 19:

0000h

1 safe state data word, safe state value for output points

Octet 20 to 21:

1920h

Slot 3 Module Key 1794-IE8 8-point analog input module

Octet 22:

10h

Slot 3 config size 1 word, safe state size 0 words

Octet 23 to 24:

0000h

1 config word, channel selection

Octet 25 to 26:

5121h

Slot 4 Module Key 1794-OE4 4-point analog output module

Octet 27:

24h

Slot 4 config size 2 words, safe state size 4 words

Octet 28 to 29:

0000h

2 config words – channel selection and
output enable

Octet 30 to 31:

0000h