How Communication Takes Place and I/O Image Table Mapping

3170-PDP ♦ FLEX Platform

FLEX I/O™ PROFIBUS Adapter

ProSoft Technology, Inc.

Page 19 of 152

August 23, 2007

3

How Communication Takes Place and I/O
Image Table Mapping

In This Chapter

¾

Polled I/O Structure................................................................ 20

¾

Mapping Data into the Image Table ....................................... 22

¾

Connection

Status

Word Definition ........................................ 42

¾

Logic Status/Analog Feedback Definition............................... 42

¾

Connection

Enable

Word Definition ....................................... 42

¾

Logic Command/Analog Reference Definition ....................... 42

¾

Defaults.................................................................................. 43

In this chapter, you will learn about:
ƒ

communication over the FLEX I/O backplane (between the PROFIBUS

adapter and the I/O modules)

ƒ

how data is mapped into the I/O image table

One 3170-PDP PROFIBUS adapter can interface with up to eight terminal base
units with installed FLEX I/O modules, forming a FLEX I/O system of up to eight
slots. The adapter communicates to other network system components over the
PROFIBUS network. The adapter communicates with its I/O modules over the
backplane.

Inputs

Status

Outputs

Configuration

Slot 1

I/O Module

Read
Words

Write

Words

0

1

Read

Write

PROFIBUS
Adapter

Inputs

Status

Outputs

Configuration

Slot 2

I/O Module

Inputs

Status

Outputs

Configuration

Slot 8

I/O Module

Network

The I/O map for a module is divided into read words and write words. Read
words consist of input and status words, and write words consist of output and
configuration words. The number of read words or write words can be 0 or more.
The length of each I/O module's read words and write words vary in size
depending on module complexity. Each I/O module will support at least 1 input
word or 1 output word. Status and configuration are optional, depending on the
module.