;Config word 4
Ext_User_Prm_Data_Ref(13) = 62
;Initiate configuration
Ext_User_Prm_Data_Ref(13) = 73
Ext_User_Prm_Data_Ref(13) = 63
Ext_User_Prm_Data_Ref(13) = 64
Ext_User_Prm_Data_Ref(13) = 88
Ext_User_Prm_Data_Ref(13) = 89
;Req output 0 to hold
Ext_User_Prm_Data_Ref(14) = 65
;Revert to defaults
Ext_User_Prm_Data_Ref(14) = 66
Ext_User_Prm_Data_Ref(14) = 67
Ext_User_Prm_Data_Ref(14) = 68
Ext_User_Prm_Data_Ref(14) = 87
Ext_User_Prm_Data_Ref(14) = 86
Ext_User_Prm_Data_Ref(14) = 85
Ext_User_Prm_Data_Ref(14) = 84
;Enable Input 0
EndModule
; Flex I/O module 1794-OW8, (default config= 0 word in, 1 word out)
Module = "1794-OW8 / Full format" 0x00, 0x60
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x01, 0x99, 0x01, 0x00, 0x00
;1 safe state word
;SS
Ext_User_Prm_Data_Ref(4) = 16
;No config
EndModule
; Flex I/O module 1793-OW4(S), (default config= 0 word in, 1 word out)
Module = "1793-OW4(S) / Full format" 0x00, 0x60
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x01, 0x15, 0x01, 0x00, 0x00
;SS word 1
Ext_User_Prm_Data_Ref(4) = 48
;4 lsb bits in low byte
EndModule
; Flex I/O module 1794-IR8, (default config= 11 words in, 0 words out)
Module = "1794-IR8 / Full format" 0x5A, 0x00
Ext_Module_Prm_Data_Len = 9
Ext_User_Prm_Data_Const(0) = 0x1B, 0x01, 0x30, 0x00, 0x00, 0x00, 0x00, 0x00, \
0x00
;Config word1
Ext_User_Prm_Data_Ref(3) = 17 ;8 bit mask
Ext_User_Prm_Data_Ref(4) = 91
Ext_User_Prm_Data_Ref(4) = 90
Ext_User_Prm_Data_Ref(4) = 18
Ext_User_Prm_Data_Ref(4) = 19
Ext_User_Prm_Data_Ref(4) = 20
;MDT
;Config word2
Ext_User_Prm_Data_Ref(5) = 24
Ext_User_Prm_Data_Ref(5) = 23
Ext_User_Prm_Data_Ref(6) = 22
Ext_User_Prm_Data_Ref(6) = 21