How Communication Takes Place and I/O Image Table Mapping

3170-PDP ♦ FLEX Platform

FLEX I/O™ PROFIBUS Adapter

ProSoft Technology, Inc.

Page 37 of 152

August 23, 2007

Word

Dec. Bits (Octal
Bits)

Description

08

(10)

Calibration Range bit – set to 1 if a reference signal is out of
range during calibration

09

(11)

Calibration Done bit – set to 1 after an initiated calibration
cycle is complete.

10

(12)

Calibration Bad bit – set to 1 if the channel has not had a
valid calibration.

11 to 15 (13 to 17) Unused – set to 0

Write word 1

00 to 01

Module Data Type

Bit 01 00

0 0 °C

(default)

0 1 °F

1

0

Bipolar counts scaled between –32768 and
+32767

1

1

Unipolar counts scaled between 0 and
65535

02 Enhanced mode select – measures voltage drop across a

precision resistor in the module to compare with the
unknown input.

03 to 05

A/D Filter First Notch Frequency

Bit 05 04 03 Definition

0 0 0 10Hz

(default)

0 0 1 25Hz

0 1 0 50Hz

0 1 1 60Hz

1 0 0 100Hz

1 0 1 250Hz

1 1 0 500Hz

1 1 1 1000hZ

06 Calibration High/Low bit – This bit is set during gain

calibration; reset during offset calibration.

07 Calibration clock – this bit must be set to 1 to prepare for a

calibration cycle; then reset to 0 to initiate calibration.

08 to 15

Calibration mask – The channel, or channels, to be
calibrated will have the correct mask bit set. Bit 0
corresponds to channel 0, bit 1 to channel 1, and so on.

Write Word 2

00 to 03

Channel 0 RTD Type

Bit 03 02 01 00 RTD Type – Range

0

0

0

0

Resistance

(default)

0

0

0

1

No sensor connected – do not scan

0

0

1

0

100 ohm Pt = 0.00385 Euro (–200 to
+870°C)

0

0

1

1

100 ohm Pt = 0.003916 U.S. (–200
to +630°C)

0

1

0

0

200 ohm Pt = 0.00385 (–200 to
+630°C)