3170-PDP ♦ FLEX Platform

Configure the Adapter for Master/Slave Communication

FLEX I/O™ PROFIBUS Adapter

Page 60 of 152

ProSoft Technology, Inc.

August 23, 2007

Check Configuration Example

Check Configuration Message when used with Send Parameter Full Format (Length 10
bytes)

Name Identifier

Byte

Description

Octet 1:

50h

Status Word (input – 1 word)

Octet 2:

60h

Output Status Word (output – 1 word)

Octet 3:

50h

Slot 1, input module 1 word

Octet 4:

00h

Slot 1, output module empty

Octet 5:

00h

Slot 2, input module empty

Octet 6:

60h

Slot 2, output module 1 word

Octet 7:

58h

Slot 3, input module 9 words

Octet 8:

00h

Slot 3, output module empty

Octet 9:

50h

Slot 4, input module 1 word

Octet 10:

63h

Slot 4, output module 4 words

I/O sizes configured: 24 input bytes, 12 output bytes

The read configuration message response returns the current configuration data.
At power up, the configuration is the maximum read and write sizes supported by
each FLEX I/O module.

5.3

Read Configuration Response Data

A valid check configuration message updates the internal configuration. The
updated internal configuration is then returned in the message response.

Power Up Configuration Example

Read Configuration Message response at Power Up (Length 10 bytes)

Name Identifier

Byte

Description

Octet 1:

50h

Status Word (input - 1 word)

Octet 2:

60h

Output Status Word (output - 1 word)

Octet 3:

51h

Slot 1, input module 2 words

Octet 4:

60h

Slot 1, output module 1 word

Octet 5:

50h

Slot 2, input module 1 word

Octet 6:

61h

Slot 2, output module 2 words

Octet 7:

58h

Slot 3, input module 9 words

Octet 8:

65h

Slot 3, output module 6 word

Octet 9:

50h

Slot 4, input module 1 word

Octet 10:

60h

Slot 4, output module 14 words

Refer to the configuration example to understand how and where to enter this
data. If you are using the Rockwell Automation PROFIBUS Manager
configuration software, follow this example to understand how to access and
enter data. This example is a User Parameter Message, Full Format.