3170-PDP ♦ FLEX Platform
How Communication Takes Place and I/O Image Table Mapping
FLEX I/O™ PROFIBUS Adapter
Page 36 of 152
ProSoft Technology, Inc.
August 23, 2007
Dec.
Bit
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Read Word 7
Channel 5 Input Data
Read Word 8
Channel 6 Input Data
Read Word 9
Channel 7 Input Data
Read Word 10 Overrange Bits
Underrange Bits
Read
Word
11
0 0 0 0 0 Bad
Cal
Cal
Done
Cal
Range
0 Diagnostic
Status
Bits
Pwr
Up
0 0 0
1794-IR8 Write
Dec.
Bit 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Oct.
Bit 17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Write Word
1
8-bit Calibration Mask
Cal
Clk
Cal Hi
Cal Lo
Filter Cutoff
Enh MDT
Write Word
2
RTD 3 Type
RTD 2 Type
RTD 1 Type
RTD 0 Type
Write Word
3
RTD 7 Type
RTD 6 Type
RTD 5 Type
RTD 4 Type
Where: Enh = Enhanced
MDT = Module Data Type
1794-IR8 Word/Bit Descriptions
Word
Dec. Bits (Octal
Bits)
Description
Read Word 1
00 to 15 (00 to 17) Reserved
Read Word 2
00 to 15 (00 to 17) Channel 0 Input data
Read Word 3
00 to 15 (00 to 17) Channel 1 Input data
Read Word 4
00 to 15 (00 to 17) Channel 2 Input data
Read Word 5
00 to 15 (00 to 17) Channel 3 Input data
Read Word 6
00 to 15 (00 to 17) Channel 4 Input data
Read Word 7
00 to 15 (00 to 17) Channel 5 Input data
Read Word 8
00 to 15 (00 to 17) Channel 6 Input data
Read Word 9
00 to 15 (00 to 17) Channel 7 Input data
Read Word 10 00 to 07
Underrange bits – these bits are set if the input signal is
below the input channel's minimum range.
08 to 15 (10 to 17) Overrange bits – these bits are set if 1), the input signal is
above the input channel's maximum range, or 2), an open
detector is detected.
Read Word 11 00 to 01
Not used – set to 0
02 Reserved
03 Powerup bit – this bit is set (1) until configuration data is
received by the module.
04 to 06
Critical Error bits – If these bits are anything other than all
zeroes, return the module to the factory for repair
07
Unused – set to 0