ProSoft Technology 3170-PDP User Manual
Page 40

3170-PDP ♦ FLEX Platform
How Communication Takes Place and I/O Image Table Mapping
FLEX I/O™ PROFIBUS Adapter
Page 40 of 152
ProSoft Technology, Inc.
August 23, 2007
Word Decimal
Bit
(Octal Bit)
Description
03
(03)
Powerup bit – this bit is set (1) until configuration data is
received by the module.
04 to 06 (04 to 06) Critical Fault bits – If these bits are anything other than zero,
return the module to the factory for repair.
07 (07)
Unused – set to 0
08
(10)
Calibration Range bit – set to 1 if a reference signal is out of
range during calibration
09
(11)
Calibration Done bit – set to 1 after an initiated calibration
cycle is complete.
10
(12)
Calibration Bad bit – set to 1 if the channel has not had a valid
calibration.
11 to 15 (13 to 17) Unused – set to 0
Write Word 1
00 to 01 (00 to 01) Module Data Type
Bit
01
00 Definition
0
0
°C
(default)
0
1
°F
1
0
Bipolar counts scaled between –32768 and +32767
1
1
Unipolar counts scaled between 0 and 65535
Bit 02 (02)
Fixed Digital Filter – When this bit is set (1), a software digital
filter is enabled. This filter settles to 100% of a Full Scale step
input in 60 scans.
03 to 05 (03 to 05) A/D Filter First Notch Frequency
Bit 05 04 03 Definition
0 0 0 10Hz
(default)
0 0 1 25Hz
0 1 0 50Hz
0 1 1 60Hz
1 0 0 100Hz
1 0 1 250Hz
1 1 0 500Hz
1 1 1 1000hZ
06
(06)
Calibration High/Low bit – This bit is set during gain
calibration; reset during offset calibration.
07
(07)
Calibration clock – this bit must be set to 1 to prepare for a
calibration cycle; then reset to 0 to initiate calibration.
08 to 15 (10 to 17) Calibration mask – The channel, or channels, to be calibrated
will have the correct mask bit set. Bit 8 corresponds to
channel 0, bit 9 to channel 1, and so on.
Write Word 2
00 to 03 (00 to 03) Channel 0 Thermocouple Type
Bit
03 02 01 00 Thermocouple Type – Range
0
0
0
0
Millivolts
(default)
0 0
0
1
300 to 1800°C
(572 to 3272°F)
0 0
1
0
–270 to 1000°C (–454 to 1832°F)