Configure the Adapter for Master/Slave Communication

3170-PDP ♦ FLEX Platform

FLEX I/O™ PROFIBUS Adapter

ProSoft Technology, Inc.

Page 57 of 152

August 23, 2007

User Parameter Message, Full Format

Name Value

Description

Octet 9:

OBh

Full Format, Use Safestate

Octet 10 to 11:

0281h

Slot 1 Module Key 1794-IB16 16-point discrete input module

Octet 12 to 13

10h

Slot 1 config size 1 word, safe state size 0 words

Octet 13 to 14:

0000h

1 config word, input delay times

Octet 15 to 16:

0191h

Slot 2 Module Key 1794-OB16 16-point discrete output module

Octet 17:

01h

Slot 2 config size 0 words, safe state size 1 word

Octet 18 to 19:

0000h

1 safe state data word, safe state value for output points

Octet 20 to 21:

1920h

Slot 3 Module Key 1794-IE8 8-point analog input module

Octet 22:

10h

Slot 3 config size 1 word, safe state size 0 words

Octet 23 to 24:

0000h

1 config word, channel selection

Octet 25 to 26:

5121h

Slot 4 Module Key 1794-OE4 4-point analog output module

Octet 27:

24h

Slot 4 config size 2 words, safe state size 4 words

Octet 28 to 29:

0000h

4 safe state data words – safe state value for output point 1
output point 2
output point 3
output point 4

Octet 30 to 31:

0000h

Octet 32 to 33:

0000h

Octet 34 to 35:

0000h

Octet 36 to 37:

0000h

2 config words – channel selection and
output enable

Octet 38 to 39:

0000h

Octet 40 to 41:

0FFFFh

Slot 5 empty

Octet 42:

00h

Slot 5 all sizes zero

Octet 43 to 44:

0FFFFh

Slot 6 empty

Octet 45:

00h

Slot 6 all sizes zero

Octet 46 to 47:

0FFFFh

Slot 7 empty

Octet 48:

00h

Slot 7 all sizes zero

Octet 49 to 50:

0FFFFh

Slot 8 Empty

Octet 51:

00h

Slot 8 all sizes zero

Octet 52 to 244 00h

Not Used

Refer to the configuration example to understand how and where to enter this
data. On a PROFIBUS DP network, the I/O data exchanged between the
PROFIBUS DP master and a DP slave is encapsulated into logical modules.
The total I/O data exchanged between a PROFIBUS DP master and a DP slave
device comprises a set of logical modules which is defined in the check
configuration data.