1203-fm1 – scanport module image table mapping – ProSoft Technology 3170-PDP User Manual

Page 41

background image

How Communication Takes Place and I/O Image Table Mapping

3170-PDP ♦ FLEX Platform

FLEX I/O™ PROFIBUS Adapter

ProSoft Technology, Inc.

Page 41 of 152

August 23, 2007

Word Decimal

Bit

(Octal Bit)

Description

0 0

1

1

–210 to 1200°C (–346 to 2192°F)

0 1

0

0

–71 to 1372°C

(–95 to 2502°F)

0 1

0

1

–50 to 1768°C

(–58 to 3214°F)

0 1

1

0

–50 to 1768°C

(–58 to 3214°F)

0 1

1

1

–73 to 400°C

(–99 to 752°F)

1 0

0

0

0 to 2315°C

(32 to 4199°F)

1 0

0

1

–270 to 1300°C (–450 to 2372°F)

1

0

1

0

Reserved

1

0

1

1

Reserved

1

1

0

0

Module reports cold junction temperature
for channels 00 to 03

1

1

0

1

Module reports cold junction temperature
for channels 04 to 07

1

1

1

0

Reserved

1 1

1

1

No sensor connected (do not scan)

04 to 07 (04 to 07) Channel 1 Thermocouple Type (see bits 00 to 03)

08 to 11 (10 to 13) Channel 2 Thermocouple Type (see bits 00 to 03)

12 to 15 (14 to 17) Channel 3 Thermocouple Type (see bits 00 to 03)

Write Word 3

00 to 03 (00 to 03) Channel 4 Thermocouple Type (see word 13, bits 00 to 03)

04 to 07 (04 to 07) Channel 5 Thermocouple Type (see word 13, bits 00 to 03)

08 to 11 (10 to 13) Channel 6 Thermocouple Type (see word 13, bits 00 to 03)

12 to 15 (14 to 17) Channel 7 Thermocouple Type (see word 13, bits 00 to 03)

3.2.12 1203-FM1 – SCANport Module Image Table Mapping

0

Connection Status Channel 1

Logic Status Channel 1

Analog Feedback Channel 1

Logic Status Channel 2

Analog Feedback Channel 2

Connection StatusChannel 2

Module Image

I/O Image

6 Words

5 Words

Read

Write

1 Word

Connection Enable Channel 2 Connection Enable Channel 1

Logic Command Channel 1

Analog Reference Channel 1

Logic Command Channel 2

Analog Reference Channel 2

Not Used