beautypg.com

ProSoft Technology 3170-PDP User Manual

Page 117

background image

Reference 3170-PDP

♦ FLEX Platform

FLEX I/O™ PROFIBUS Adapter

ProSoft Technology, Inc.

Page 117 of 152

August 23, 2007

; Flex I/O module 1793-IB4(S), (default config= 2 word in, 0 word out)

Module = "1793-IB4(S) / Full format" 0x51, 0x00

Ext_Module_Prm_Data_Len = 5

Ext_User_Prm_Data_Const(0) = 0x02, 0x0C, 0x10, 0x00, 0x00

;Config word 1

Ext_User_Prm_Data_Ref(4) = 47

EndModule

; Flex I/O module 1793-OB4P(S), (default config= 0 word in, 1 word out)

Module = "1793-OB4P(S) / Full format" 0x00, 0x60

Ext_Module_Prm_Data_Len = 5

Ext_User_Prm_Data_Const(0) = 0x01, 0x10, 0x01, 0x00, 0x00

;Safe state word

Ext_User_Prm_Data_Ref(4) = 48

EndModule

; Flex I/O module 1793-IB2XOB2P(S), (default config= 1 word in, 2 word out)

Module = "1793-IB2XOB2P(S) / Full format" 0x50, 0x60

Ext_Module_Prm_Data_Len = 7

Ext_User_Prm_Data_Const(0) = 0x01, 0x11, 0x11, 0x00, 0x00, 0x00, 0x00

;Safe state word 1

Ext_User_Prm_Data_Ref(4) = 49

;Config word 1

Ext_User_Prm_Data_Ref(6) = 50

EndModule

; Flex I/O module 1794-IB32/A, (default config= 2 word in, 0 word out)

Module = "1794-IB32 / Full format" 0x51, 0x00

Ext_Module_Prm_Data_Len = 5

Ext_User_Prm_Data_Const(0) = 0x02, 0x11, 0x10, 0x00, 0x00

;Config word 1

Ext_User_Prm_Data_Ref(4) = 256;

EndModule

; Flex I/O module 1794-OB32P, (default config= 0 word in, 2 word out)

Module = "1794-OB32P / Full format" 0x00, 0x61

Ext_Module_Prm_Data_Len = 7

Ext_User_Prm_Data_Const(0) = 0x00, 0x01, 0x02, 0x00, 0x00, 0x00, 0x00

; 2 Safe state words

Ext_User_Prm_Data_Ref(3) = 7;

Ext_User_Prm_Data_Ref(5) = 8;

EndModule

; Flex I/O module 1794-IB16XOB16P, (default config= 1 word in, 1 word out)

Module = "1794-IB16XOB16P / Full format" 0x50, 0x60

Ext_Module_Prm_Data_Len = 7

Ext_User_Prm_Data_Const(0) = 0x01, 0x1C, 0x11, 0x00, 0x00, 0x00, 0x00

; 1 Safe state word

Ext_User_Prm_Data_Ref(3) = 7;

; 1 Config word