Ext_User_Prm_Data_Const(0) = 0x01, 0x04, 0x01, 0x00, 0x00
;Safe state word 1
Ext_User_Prm_Data_Ref(3) = 7
EndModule
; Flex I/O module 1794-OV16P, (default config= 0 word in, 1 word out)
Module = "1794-OV16P / Full format" 0x00, 0x60
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x01, 0x09, 0x01, 0x00, 0x00
;Safe state word 1
Ext_User_Prm_Data_Ref(3) = 7
EndModule
; Flex I/O module 1793-OV16P/A, S/A, (default config= 0 word in, 1 word out)
Module = "1793-OV16P/A, S/A / Full format" 0x00, 0x60
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x01, 0x19, 0x01, 0x00, 0x00
;Safe state word 1
Ext_User_Prm_Data_Ref(3) = 7
EndModule
; Flex I/O module 1794-OB8EP, (default config= 1 word in, 2 word out)
Module = "1794-OB8EP / Full format" 0x50, 0x61
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x01, 0x9D, 0x01, 0x00, 0x00
;Safe state word 1
Ext_User_Prm_Data_Ref(3) = 7
EndModule
; Flex I/O module 1794-IBI0XOB6, (default config= 1 word in, 1 word out)
Module = "1794-IB10XOB6 / Full format" 0x50, 0x60
Ext_Module_Prm_Data_Len = 7
Ext_User_Prm_Data_Const(0) = 0x01, 0x00, 0x11, 0x00, 0x00, 0x00, 0x00
;Safe state word 1
Ext_User_Prm_Data_Ref(4) = 16
;Config word 1
Ext_User_Prm_Data_Ref(5) = 45
EndModule
; Flex I/O module 1794-IC16, (default config= 2 word in, 0 word out)
Module = "1794-IC16 / Full format" 0x51, 0x00
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x02, 0x08, 0x10, 0x00, 0x00
;Config word 1
Ext_User_Prm_Data_Ref(4) = 45
Ext_User_Prm_Data_Ref(4) = 46
EndModule
; Flex I/O module 1794-OC16, (default config= 1 word in, 1 word out)
Module = "1794-OC16 / Full format" 0x50, 0x60
Ext_Module_Prm_Data_Len = 5
Ext_User_Prm_Data_Const(0) = 0x01, 0x0C, 0x01, 0x00, 0x00
;Safe state word 1
Ext_User_Prm_Data_Ref(3) = 7
EndModule