Connect the Adapter to the PROFIBUS DP Network

3170-PDP ♦ FLEX Platform

FLEX I/O™ PROFIBUS Adapter

ProSoft Technology, Inc.

Page 49 of 152

August 23, 2007

3

Insert the wired connector into the mating connector on the PROFIBUS
adapter.

RTS (Pin 4) Optional pin. Not used in a standard RS455 PROFIBUS – DP
installation.

4.5 Terminate

the

Network

You must use termination blocks only if your devices on the end of the network
do not have built-in terminating resistors.

Terminate the PROFIBUS media (trunk cable) at both ends of the network. If you
are not using a connector with built-in resistors, terminate the cable at the
adapter connector as shown below.

4.5.1 Terminate at the Adapter Using Line A

Since Line A has a higher line impedance, you must use the following termination
resistors:

PROFIBUS DP ADAPTER

+ 5 V

6

3

8

5

390 W (2%, 1/4 W)

390 W (2%, 1/4 W)

CABLE

Signal +

Signal -

Data Ground

220 W (2%, 1/4 W)

5

.

.

1

9

6

.

.

4.5.2 Terminate at the Adapter Using Line B

Use the following termination resistors with line B:

PROFIBUS DP ADAPTER

+ 5 V

6

3

8

5

390 W (2%, 1/4 W)

390 W (2%, 1/4 W)

CABLE

Signal +

Signal -

Data Ground

150 W (2%, 1/4 W)

5

.

.

1

9

6

.

.