Configuring the MVI56E-MNET Module

MVI56E-MNET / MNETXT ♦ ControlLogix Platform

User Manual

Modbus TCP/IP Interface Module

Page 64 of 181

ProSoft Technology, Inc.

April 23, 2014

If the Test Connection procedure fails, you will see an error message. To correct
the error, follow these steps.

1 Click OK

to dismiss the error message.

2 In the Download

dialog box, click B

ROWSE

D

EVICE

(

S

) to open ProSoft

Discovery Service.

3 Select the module, and then click the right mouse button to open a shortcut

menu. On the shortcut menu, choose S

ELECT FOR

PCB.

4 Close ProSoft Discovery Service.
5 Click D

OWNLOAD

to transfer the configuration to the module.

2.4.1 Using CIPconnect to Connect to the Module

You can use CIPconnect

®

to connect a PC to the MVI56E-MNET module over

Ethernet using Rockwell Automation’s 1756-ENBT EtherNet/IP

®

module. This

allows you to configure the MVI56E-MNET module and network, upload and
download files, and view network and module diagnostics from a PC. RSLinx is
not required when you use CIPconnect. All you need are:
 The IP addresses and slot numbers of any 1756-ENBT modules in the path
 The ControlNet node numbers and slot numbers of any 1756-CNBx

ControlNet Bridge modules in the path

 The slot number of the MVI56E-MNET in the destination ControlLogix chassis

(the last ENBT/CNBx and chassis in the path).

To use CIPconnect, follow these steps.